Product label includes basic specification of product and A/S information.  

Product label is attached on the outer side of each unit.

Please make sure that the label on purchased product is the same specification what you ordered.

3

1. IDENTIFICATION

1. NO of 
Phase

S :  Single 

Phase

T : Three 

Phase

2. Product

Model

E. E TYPE

3. Rated 
Voltage

1. 110V

2. 220V

3. 380V

4. 440V

4. Rated

Current

25A~70A

5. OPTION

F : With Fuse

Blank : 
Without Fuse

6. OPTION

FN : With 
Cooling Fan

Blank : 
Without 
Cooling Fan

T      E      2   – 0   2   5 – F   - FN

PARA-ENT

Republic of Korea

+(82)-31-831-8310

Product 

: Power Regulator

Model 

: TE2 - 025 -

-

Power Rating 

: 25A @ 220V, 50/60Hz                       

Input 

: 4~20mA

Made In Korea

H.page :,  A/S 031)831-8312

1.1. IDENTIFICATION CODE

1.2. PRODUCT LABEL

Must preserve notices during handling the machine to ensure safety. 

Summary of Contents for TE Series

Page 1: ...USER S MANUAL TE TYPE VER 1 00...

Page 2: ...achine or component is altered voluntarily When a problem occurs please contact our company s A S Department 7 Check and repair 1 Before checking the machine cut off the power and beware of electric s...

Page 3: ...Product Model E E TYPE 3 Rated Voltage 1 110V 2 220V 3 380V 4 440V 4 Rated Current 25A 70A 5 OPTION F With Fuse Blank Without Fuse 6 OPTION FN With Cooling Fan Blank Without Cooling Fan T E 2 0 2 5 F...

Page 4: ...Transformer coupled load Zero Crossing Resistive load only Minimum Load 1A Control Input Auto 4 20mA Default 0 20mA 0 5VDC 1 5VDC 0 10VDC Option Manual Outer 10K potentiometer Selecting Method Selecti...

Page 5: ...inside of panel 3 Fasten the mounting bolt NO 8 in name of each part tightly 4 2 1 VENTILATIO AND COOLING 1 This product is cooled by nature and by cooling fan 55 70A Basically with cooling fan 2 In c...

Page 6: ...t signal Connect mechanic relay no voltage onto Run Stop Alarm relay is N O Normal open 6 3 OUTPUT VOLUME DIP SWITCH 3 OFF Using inner volume on page 5 ON Using manual volume of 10k 6 4 SELECTING CONT...

Page 7: ...dip switch should be on to adjust inner output volume Please check it out for proper use before operation You can not use manual input 10K and outer output volume 10K together 7 4 ADJUSTING OUTPUT VOL...

Page 8: ...n each phase is less than 1A Or when fuse is burnt Blink Failure of SCR When input signal is 0 and output current on each phase is more than 1A Blink Over Current Output current is more than 120 than...