Parameter 2:
you may choose
Add
or
Sub
to adjust inverter B
voltage*
Parameter 3:
the voltage range is from 0V to 9.9V, the default
value is 0V.
*The number 1 under the
or
represent the
inverter B
Inverter C voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust inverter C
voltage*
Parameter 3:
the voltage range is from 0V to 9.9V, the default
value is 0V.
*The number 2 under the
or
represent the
inverter C
After adjusting the inverter voltage, check whether the output voltage detecting is ok or not. Entering the
pictures as below via LCD, the LCD will display the output voltage detected. If the difference between the display
value and the voltage measured by mutimeter is more than 1V, adjusting it to make sure the difference is no
more than 1V. Then shut down the UPS to save this setting into EEPROM.
Output A voltage calibration
Interface
Setting
Parameter 2:
it always shows
OP.V
as output voltage.
Parameter 3:
it shows the internal measurement value of the
output A voltage, and you can calibrate it by pressing
Up
or
Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing
Enter
. The
calibration range is limited /-9V. This function is normally
used for parallel operation.
Output B voltage calibration
Interface
Setting
Parameter 2:
it always shows
OP.V
as output voltage*.
Parameter 3:
it shows the internal measurement value of the
output B voltage, and you can calibrate it by pressing
Up
or
Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing
Enter
. The
calibration range is limited /-9V. This function is normally
used for parallel operation.