background image

TROUBLESHOOTING TIPS

Problem

Nothing happens when a setpoint occurs to turn the load ON or OFF.

Solution

Review programmed setpoints making sure the day has not been
skipped.

Problem

You wish to clear the control’s memory and start over.

Solution

Depress the reset switch to the right of the display.

Problem 

Manual override does not work.

Solution

Check the load for proper wiring. Remember, the contacts on these
units only switch what is applied to them. (Dry or isolated contacts.)

Problem

Blank display

Solution

Check the input power source, ensure proper connection.

Problem

Control does not operate after programming.

Solution

If programming was not performed (changing clock time or entering a
setpoint), the control will not update itself. Press the ENTER key and
override the load until the next scheduled setpoint.

TO REVIEW SETPOINTS

STEP

KEY

DESCRIPTION

1.

MODE

Advances from RUN mode to SET TIME
mode. (TOD displays.)

2.

MODE

Advances from SET TIME mode to SKIP-A-
DAY PROGRAMMING mode.

3.

MODE

Advances from SKIP-A-DAY PROGRAMMING
mode to EVENT PROGRAMMING mode. The
control will display the first event (1 displays at
bottom.) To modify the event, go to step 2 of
the EVENT PROGRAMMING mode 
instructions.

4.

Advance through the remaining setpoints.

5.

RUN

Returns to RUN mode when done reviewing
setpoints.

OVERRIDE:

Manual override reverses the current output state. Loads that are ON
turn immediately OFF; loads that are OFF turn immediately ON. The
timer displays OVR to indicate that the current load state is the result
of an override. The override remains in effect until overridden again or
until the next setpoint is reached. To initiate override, press OVR
(ENTER) key while in the RUN mode.

NOTE: After an override has been initiated, the OVR will display until
the next programmed setpoint is reached, even if the timer is overrid-
den again. Display will show if the load is ON or OFF.

N

L

(24, 120 or 277)

L2

L1

(208 or 240)

N

L

(120 or 277V)

L2

L1

(208 or 240V)

SPDT

SPST

DPST

1

H1

4

1

2

3

4

3

2

120V jumpers

208 or 240V jumpers

See jumpers below

L

N (120v)

L1

L2 (208 or 240V)

L

N (277V no

jumpers needed)

Typical Wiring Diagrams

H3

H2

H4

H1

H3

H2

H4

Maple Chase Company

2820 Thatcher Road
Downers Grove, Illinois 60515
Made in Mexico

Customer Service

800-951-5526

Technical Support

800-732-8400

ISO 9002 registered

Paragon Electric Canada, Ltd.

5785 Kennedy Road
Mississauga, Ontario L4Z 2G3

From outside North America
630-719-5500

Reviews: