background image

6

7

2.3

Zone Output Wiring

The “Liberator 9000” is not a stand-alone alarm system

, it must be used in

conjunction with another control panel. If you wish to generate an alarm when the
output on the receiver is toggled, connect the receiver’s zone outputs directly to the
control panel inputs and the "

COM

" terminal of the receiver to the "

COM

" terminal of

the control panel as shown in figure 2-1. Alternatively, the receiver's zone outputs
can be connected to another device such as an LED or relay. When a transmitter
generates an alarm condition, it will send a signal to the receiver which will toggle
the appropriate zone output and if the receiver’s zone outputs are connected to the
control panel inputs, the control panel will generate an alarm. The receiver may also
toggle the receiver’s zone output if the transmitter sends a trouble signal (i.e. low
battery), which the receiver has been programmed to supervise (see 

Supervision

Features

in section 6).

EOL resistors are not incorporated into the receiver’s zone outputs. If your
installation requires the use of EOL resistors, they must be added to the
receiver’s zone outputs

The Paradox ATZ (Zone Doubling) feature will not function with the wireless
system.

2.4

Connecting Keypads

To program the receiver, you must connect a service keypad (616, 626 or 633) to
the receiver. The keypad connected to the control panel will not display any trouble
conditions nor can it be used to program the receiver. The control panel keypad will
only display zone status if the receiver’s zone output has been wired to a control
panel’s input as described in section 2.3. Using a keypad with a serial connector,
connect the keypad to the serial terminal on the receiver labeled "service keypad"
(see figure 2-1). The receiver’s keypad will allow you to view the receiver’s trouble
status (see 

Trouble Display Mode

in section 6.5) and zone status. 

We do not recommend programming the receiver using LCD keypads, as
these will not correctly display programming, zone or trouble status.

Libeei03.qxd  02/28/2001  11:53 AM  Page 6

Summary of Contents for Liberator 9000

Page 1: ...Libeei03 qxd 02 28 2001 11 53 AM Page i...

Page 2: ...2 4 3 Switch Zone Assignment 13 4 4 View Transmitter Serial Numbers 14 4 5 Erase Specific Zone 14 4 6 Zone Output State 15 REMOTE CONTROL ASSIGNMENT 16 5 1 Automatic Remote Control Assignment 16 5 2 V...

Page 3: ...ntages Quick simple installation Cost reduction due to ease of installation Minimal damage to property due to installation Also ideal for temporary installations The wireless transmitters are battery...

Page 4: ...ting case and snap into place see figure 2 1 If placed correctly the antennas will lean directly over the groves in the mounting case After completing wiring as detailed in sections 2 2 to 2 4 run the...

Page 5: ...vision Features in section 6 EOL resistors are not incorporated into the receiver s zone outputs If your installation requires the use of EOL resistors they must be added to the receiver s zone output...

Page 6: ...ve the installer lock program any 3 digit value other than 147 into address 020 To enter the programming mode press ENTER Installer Code 8 9 2 5 Hand Held Remote Controls The Liberator 9000 also suppo...

Page 7: ...Two transmitters are being added to an installation consisting of four transmitters which have been assigned zones 1 through 4 Set the receiver in Automatic Zone Assignment Mode by pressing ENTER Ins...

Page 8: ...s not exist or that has already been assigned to a zone output 12 13 Example A transmitter is being added to an installation consisting of four transmitters which have been assigned zone outputs 1 2 a...

Page 9: ...igned press one of the lit keys which correspond to an assigned zone output To view the serial number of a transmitter which hasn t been assigned press and release the transmitter s tamper switch For...

Page 10: ...exist or that has already been assigned 16 17 REMOTE CONTROL ASSIGNMENT As soon as a remote control is assigned to the receiver it will reserve zone outputs 7 to 9 These outputs are activated by pres...

Page 11: ...already been assigned to zone output 12 the receiver will erase the zone assignment and enable low battery supervision Trigger Zone When a transmitter sends a low battery signal the receiver will tri...

Page 12: ...1 When using this option you will not be able to differentiate between an open zone and a low battery as they will both trigger the zone output 6 2 Check In Supervision Address 010 Keys 4 5 The receiv...

Page 13: ...condition s as described in the table below To view the zones causing the trouble failure press the desired trouble key 1 to 3 after which keys 1 through 12 represent zones 1 through 12 Any lit keys...

Page 14: ...nce of the security system Seller obligation and liability under this warranty is expressly limited to repairing or replacing at Seller s option any product not meeting the specifications In no event...

Page 15: ...Libeei03 qxd 02 28 2001 11 53 AM Page 26...

Reviews: