background image

IPR512: IP Monitoring Receiver

5 of 8

Quick Start 

Step 11: Set Supervision Loss Report Code

The Paradox reporting module will send a presence message (~100 bytes) at intervals defined by the Module Polling Time. 
If the receiver does not receive at least one presence message from the module within the Receiver Supervision Time, the 
receiver can report a communication loss to the Automation Software. For more information, see “Step 12: Set Security 
Profile” on page 6

1.

On the Receiver Configuration page, scroll to the bottom of the page. Highlight the 

Account supervision loss

 event.

2.

Click the 

Edit

 button.

3.

Select the 

Enabled

 check box to activate reporting of the selected event.

4.

In the Code column, enter a report code (3 digits for CID format, 2 alphanumerics characters for SIA format). This 
report code will be reported in CID or SIA format to the Automation Software whenever the selected event occurs. The 
receiver uses the same report format used by the registered account. 

5.

Click the blue 

Save

 link.

 

2

1

5

3

4

Summary of Contents for IPR512

Page 1: ...r viewed Connect a serial cable between the receiver s COM2 DB9 connector and a COM port on the serial printer or PC gender changer is included Out of the Box included Additional Items Required not in...

Page 2: ...ervice Provider ISP Note WAN2 is not available on the present version Check the Web for updates Step 5 Connect Power Connect the AC power cable included between the plug at the back of the receiver an...

Page 3: ...nd Subnet Mask that will permit access to the receiver on your network Perform the following to change the receiver s default IP Address and Subnet Mask 1 Press OK on the receiver to access the Main M...

Page 4: ...et the Receiver ID and Line ID 00 to 99 and Line 00 to 34 5 Select the ACK NACK protocol check box if you want the receiver to supervise communication with the Automation Software 6 In the PC column a...

Page 5: ...information see Step 12 Set Security Profile on page 6 1 On the Receiver Configuration page scroll to the bottom of the page Highlight the Account supervision loss event 2 Click the Edit button 3 Sele...

Page 6: ...click Security Profiles 2 Click the Add button 3 Type a name for the new security profile 4 In the Module Polling Time column type a 2 digit value and select a base time from the drop down list Repre...

Page 7: ...s completes installation and setup of the IPR512 Trouble and LED Display Trouble Display If a trouble occurs on the receiver the TROUBLE LED will turn on and the screen will display XX Troubles click...

Page 8: ...12 EQ01 10 2008 2008 Paradox Security Systems Ltd All rights reserved Specifications may change without prior notice One or more of the following US patents may apply 7046142 6215399 6111256 6104319 5...