WEAK/BAD/DISCONNECTED BATTERY
The UPS automatically tests the battery’s condition. If the battery is weak, bad
or disconnected, the Weak/Bad/Disconnected Battery icon will illuminate, er-
ror code Er15 will be displayed and the audible alarm will beep three times
every five-minutes until the battery is reconnected, replaced or passes a self
test. It is recommended that the UPS be allowed to charge overnight before
performing a battery test to confirm a Weak/Bad Battery condition.
NOTE:
The audible alarm cannot be silenced during this condition.
OVERLOAD
When the amount of load attached to the UPS is > 106% of its power rating;
the Overload icon will illuminate, the error code Er02 will be displayed and the
audible alarm will beep continuously. This alarm will remain on until the excess
load is removed or the UPS’s self protection circuit shuts the UPS down. If the
UPS shuts down because of an Overload condition, the UPS must perform an
Inverter function or a Self Test to clear the Overload Alarm.
NOTE:
The
audible alarm cannot be silenced during this condition.
ALARMS
ON BATTERY
When the UPS is operating on the batteries, the On-Battery icon will illumi-
nate, the Utility power LED (Green) will extinguish and the audible alarm will
sound one beep every ten-seconds. The audible alarm can be silenced dur-
ing this condition. The alarm will stop once the UPS returns to the AC normal
mode.
LOW BATTERY WARNING
When the UPS is operating on the batteries and the battery reserve is running
low, the audible alarm will sound two beeps every five-seconds and error code
Er17 will be displayed. This condition will continue until AC returns or the UPS
shuts down from battery exhaustion.
NOTE:
The audible alarm cannot be
silenced during this condition.
UPS FAULT
When the UPS detects a hardware and/or internal fault, the Fault icon will
illuminate and the audible alarm will beep continuously. The fault condition, in
some instances, may be reset by turning the UPS off and then on again.
NOTE:
The audible alarm cannot be silenced during this condition.
(These items may require optional software or hardware)
Function
Factory
Default
Description
User Choices
Set
inverter
output
voltage
Shut-
down
Type
Set
audible
alarm
state
Enable/
Disable
auto
restart
Battery
replace
date
Battery
install
date
Date of
manufac-
ture
5 years from
the install
date
Enabled
Enabled
Entire UPS
120VAC
Date of battery
replacement -
month/day/year
XX/XX/XXXX
Date of the next
battery re-
placement -
month/day/year
XX/XX/XXXX
Enable
or
Disable
Enabled, at
low battery,
disabled
Entire UPS or
UPS output
110, 120,
127VAC
Enter the date of the next battery
replacement.
Enter the current date when
replacing batteries.
Changes the output voltage.
Enabled - the UPS will emit a short
beep when in the battery mode.
At Low Battery the UPS will emit
two beeps from low battery warn-
ing until shutdown.
Disabled - Use only when soft-
ware is controlling the UPS or to
silence the alarm.
When enabled, the UPS will
automatically restart from a low
battery shutdown when normal AC
returns.
Enable/
Disable
ECO
Disabled
Enable
or
Disable
Enabled - the UPS will operate in
the Economy mode.
Entire UPS - Turns off the entire UPS.
UPS Output - Turns off the UPS's
output receptacles only.
Chapter 5: Configurable Parameters
and Settings
Enable/
Disable
Load
Shed-
ding
Disabled
Enable,
Disable or
Configure
Enabled - the specified outlet
bank will turn off.
Configure - the specified outlet
bank will turn on or off based on
the selected event.
SITE WIRING FAULT
If the Site Wiring Fault icon is illuminated and error code Er16 is displayed,
the UPS is plugged into an improperly wired AC wall outlet. If the UPS indi-
cates a Site Wiring Fault have a Qualified Electrician correct the problem.