SMARTZONE UPS USER MANUAL
66
system.
Note:
This feature is only supported in a parallel mode system.
After making all the necessary changes on this page, press the “Save Config” button to
save the changes.
Press the down arrow to go to the next battery setup page. Press the up arrow to go to
the previous battery setup page. Press the up and over arrow to return to the Advanced
Setup Menu page.
Figure 51: Battery Setup Page 3 (3-Phase UPS)
On the Installed Date line, press the number in front of the Year to type in the install
year, press the number in front of the Month to type in the install month, and press the
number in front of the Day to type in the install day. The default values for the year,
month and day are based on when the battery was fully charged at build time. The user
should change this date to the UPS install date at completion of installation.
The system is programmed to alarm 1095 days (3 years) after the set installed Date.
The user may adjust the replacement notification and alarm by reducing the 1095 days
by the number of days specified in the next two fields.
On the Battery Replacement Notification line, press the number in front of the Day to
type in the number of days less than 1095 days from the install date when the UPS will
notify the user (via a warning) that the battery cartridges are near end of life The default
is 372 days. This value has a range from 0 to 730 days. If the default value is not