SMARTZONE UPS USER MANUAL
46
Figure 25: Status Information Page 2 (3-Phase UPS)
The second page contains the status of the three dry contact points (battery switch,
input switch, and bypass switch).
Press the down arrow to go to the next Status Information page. Press the up arrow to
go to the previous Status Information page. Press the up and over arrow to return to the
Status Menu page.
Figure 26: Status Information Page 3 (3-Phase UPS)
The third page contains the Generator Access status. The Generator Access point is
sensed through an IN dry contact port on the back of the UPS. When a generator is
connected to the UPS, the generator feedback must be connected to an IN dry contact
point on the back of the UPS. This contact point must be configured to Generator (see
Advanced Settings). This page also contains the Ambient Temperature at the input side