Panduit PN380 User Manual Download Page 19

PANDUIT

 DPoE Power System User’s Guide 

 

Issue 1.0 

 

 

Part Number: PN380 

 

 

Parameter 

Description 

Default Setting 

BDT TIME MNT 

Sets the length of time (minutes) that the battery test will 
run. 

30 min. 

BDT ALRM 
Voltage 

Sets the voltage at which an alarm will be generated if the 
battery voltage falls below this level during the battery 
test. 

52 VDC 

BD ABRT Voltage 

The voltage at which the battery discharge test will abort 
if the system voltage drops below this level. 

42 VDC 

BD TEST CONST 

Sets the alarm constant for the battery test.  0 will disable 
thermal compensation effects during a battery test. 1 will 
take thermal compensation into account during the 
battery test. 

T COMP status 

Enables thermal compensation.  Thermal compensation 
adjusts the float voltage of the rectifiers to increase or 
decrease the temperature of the batteries. 

Disabled 

T START T 

The high temperature at which the controller activates 
thermal compensation. 

35° C 

T SLOPE T 

The slope value at which the controller will reduce the 
float voltage per degree if thermal compensation is active. 

72 mV/°C 

STOP VLT V 

The minimum voltage to which the controller will reduce 
plant voltage for thermal compensation. 

50.5 VDC 

T SENSE 

Selects temperature sensing device to use for battery 
temperature compensation; Internal sensor or external 
temperature probes. The controller will autosense when 
an external probe is attached and automatically adjusts 
value to external. 

External 

TL START T 

The low temperature at which the controller activates 
thermal compensation. 

-20° C  

TL SLOPE T 

The slope value at which the controller will increase the 
float voltage per degree if low thermal compensation is 
active. 

0 mV/°C 

STOP VLT V 

The maximum voltage to which the controller will increase 
the plant voltage for thermal compensation. 

56 VDC 

T RUNAWY T 

The temperature at which the controller will activate 
thermal runaway. 

60 °C 

T RUNAWY V 

The voltage to which the rectifiers will reduce for 
temperatures above T RUNAWAY T. 

50 VDC 

TEMP IS 

Selects the units the temperature reading are given in 
either Celsius or Fahrenheit. 

Celsius 

BOOST status 

Enables or disables the boost charge tests.  The boost 
feature will increase the output voltage of the rectifiers for 
a short time, usually to charge the batteries. 

Disabled 

BOOST V 

The voltage to which the boost charge test will increase, 
once the feature is activated. 

56.5 VDC 

BOOST H 

The length of time (hours) the boost charge test will run. 

12 hours 

High temperature 
alarm threshold 
(NIC card only) 

High temperature value at which the controller will trigger 
a HIGH TEMP alarm.  (For systems using the NIC card 
only.) 

98 °C 

 

 

  

14

 

 

Summary of Contents for PN380

Page 1: ...DPoE Power System User s Guide Issue 1 0 Part Number PN380 February 2005 2005 PANDUIT Corp All Rights reserved www panduit com...

Page 2: ...lies with Part 15 of FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including i...

Page 3: ...implied PANDUIT Corp specifically disclaims the implied warranties of merchantability and fitness for a particular purpose The remedies provided herein are Buyer s sole and exclusive remedies PANDUIT...

Page 4: ...rt Circuit and Current Limit 12 Troubleshooting 12 NIC Information 12 NIC Card Settings 13 Figures Figure 1 Individual AC Feed Wiring Architecture 4 Figure 2 DC Wire Diagram 5 Figure 3 Connecting to a...

Page 5: ...on 3 Table 4 Recommended AC Circuit Breaker and Wire Sizes 4 Table 5 Minimum Recommended DC AWG for 90 C Cabling for Unprotected Outputs 7 Table 6 Recommended Torque Settings 7 Table 7 PANDUIT Corpora...

Page 6: ...pport all the Powered Devices PD connected to the panel In these cases or in cases of multiple DPoE Power Patch Panels a larger power system is often required One option is to use the PANDUIT DPoE Pow...

Page 7: ...ch chassis should be fed from a dedicated AC branch circuit of a TN or IT power system CAUTION The plug ends on the power cords used for the AC connections are considered to be the primary disconnect...

Page 8: ...s of 10 from PANDUIT part number DPoEPWRF10 Fuses are also available from Littelfuse and Bussman Their part numbers are as follows Littelfuse 481 series 10 Amp fuse part number 0481010 Bussman Fast Ac...

Page 9: ...5 14 DC Output Wiring Sizing There are two main considerations for sizing DC wire ampacity and voltage drop Ampacity refers to the safe current carrying level as specified by U S based organizations s...

Page 10: ...rews The bulk DC connection may be used as a battery input or as an unfused bulk output The connections require a terminal lug 1 4 single hole lug with a max tongue width of 0 63 or less Size wires ba...

Page 11: ...e included power harness has two wires for the A feed power only pins 1 2 The DPoE Power Patch Panel supports an optional redundant B feed power option but the terminals and wire leads are not attache...

Page 12: ...with a minimum number of commonly available tools 1 2 flat blade and Phillips head screwdrivers Torque wrench 7 16 socket drive Wire and cable strippers PANDUIT part number CT 100 Wire and cable crimp...

Page 13: ...ng boxes until the chassis wiring is complete Power Plant Mounting and Wiring WARNING Ensure all AC and DC power sources are off and disconnected Mechanical Mounting The DPoE Power System chassis is i...

Page 14: ...wer System User s Guide Issue 1 0 Part Number PN380 IEC320 AC cord Cord Bracket Securing Screw Figure 5 Cord Bracket Figure 6 Chassis Rear View AC Connections 4 40 Screws Figure 7 Securing Cord Bracke...

Page 15: ...C connection requires properly crimped terminal lugs 1 4 single hole lug with a max tongue width of 0 63 or less Terminal lugs such as PANDUIT part number LCA4 14 L for use with 3 or 4 AWG stranded wi...

Page 16: ...lease the latch handle Pull the latch handle until the rectifier clears the rear connector on the chassis then gently slide it out of the rear connector With the latch handle open on the replacement r...

Page 17: ...latched into their respective slots Make sure all power and signal connectors are properly mated Table 8 Troubleshooting Alarm Problem Possible Solution DC OK LED is extinguished This rectifier has s...

Page 18: ...Power System EMS Webpage via IPSetup exe on the CD provided with the chassis DPoEPWRCM only The NIC card will also work with Telnet or SNMP NIC Card Settings The NIC card comes equipped with the follo...

Page 19: ...ature sensing device to use for battery temperature compensation Internal sensor or external temperature probes The controller will autosense when an external probe is attached and automatically adjus...

Page 20: ...t Number PN380 15 Parameter Description Default Setting High temperature alarm release NIC Card only The temperature value at which the controller will release a HIGH TEMP alarm For systems using the...

Reviews: