Panduit PN380 User Manual Download Page 17

PANDUIT

 DPoE Power System User’s Guide 

 

Issue 1.0 

 

 

Part Number: PN380 

 

 

Short Circuit and Current Limit 

I

Limit

 can be adjusted up to +105% of the rated current of the rectifier (See 

Table 4: Recommended AC 

Circuit Breaker and Wire Sizes

).  The system voltage will remain constant up to I

Limit

 at which point the 

system voltage will drop quickly toward 0 VDC

,

 as shown in 

Figure 11: Short Circuit & Current Limit

.  

Once a rectifier output drops below 12 VDC for more than 5 seconds, the system will shut down.  The 
system will automatically restart after 60 seconds, and will continue until the short circuit is cleared.   

 

 

 

 

 

 

 
 
 

I

Limit

 

Current

V

Shutdown

 

Rectifier Voltage 

V

Rated

 

Figure 11: Short Circuit & Current Limit 

Troubleshooting 

 
The modular nature of this DPoE Power System makes diagnostics and repair easy. Make sure that all 
rectifiers are properly seated and latched into their respective slots. Make sure all power and signal 
connectors are properly mated.  
 

Table 8: Troubleshooting 

Alarm 

Problem 

Possible Solution 

DC OK LED is extinguished 

This rectifier has stopped 
outputting power 

Rectifier failed.  Replace this 
unit.  

AC OK and all LEDs are 
extinguished 

Commercial power has been 
lost to the specified rectifier(s) 

Reset commercial circuit 
breaker to the dedicated AC 
circuit that feeds the system.  
Seek alternative power source 
until power is restored. 

Fuse Open 

A fuse is in the open state 

Replace the open fuse 

 

NIC Information  

 
The 

PANDUIT

 DPoE Power System Chassis can be ordered with or without the NIC card.  (PANDUIT 

part number DPoEPWRCM includes the NIC card.  PANDUIT part number DPoEPWRCU does not).  The 
NIC card allows the DPoE Power System to communicate with the management system.  If a chassis is 
ordered and installed without a NIC card, it can be easily field upgraded to add the NIC card. 

Figure 8: 

Chassis (Front View) - GMT fuse holder

 shows where the NIC card is plugged into the chassis.  

 

 

  

12

 

 

Summary of Contents for PN380

Page 1: ...DPoE Power System User s Guide Issue 1 0 Part Number PN380 February 2005 2005 PANDUIT Corp All Rights reserved www panduit com...

Page 2: ...lies with Part 15 of FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including i...

Page 3: ...implied PANDUIT Corp specifically disclaims the implied warranties of merchantability and fitness for a particular purpose The remedies provided herein are Buyer s sole and exclusive remedies PANDUIT...

Page 4: ...rt Circuit and Current Limit 12 Troubleshooting 12 NIC Information 12 NIC Card Settings 13 Figures Figure 1 Individual AC Feed Wiring Architecture 4 Figure 2 DC Wire Diagram 5 Figure 3 Connecting to a...

Page 5: ...on 3 Table 4 Recommended AC Circuit Breaker and Wire Sizes 4 Table 5 Minimum Recommended DC AWG for 90 C Cabling for Unprotected Outputs 7 Table 6 Recommended Torque Settings 7 Table 7 PANDUIT Corpora...

Page 6: ...pport all the Powered Devices PD connected to the panel In these cases or in cases of multiple DPoE Power Patch Panels a larger power system is often required One option is to use the PANDUIT DPoE Pow...

Page 7: ...ch chassis should be fed from a dedicated AC branch circuit of a TN or IT power system CAUTION The plug ends on the power cords used for the AC connections are considered to be the primary disconnect...

Page 8: ...s of 10 from PANDUIT part number DPoEPWRF10 Fuses are also available from Littelfuse and Bussman Their part numbers are as follows Littelfuse 481 series 10 Amp fuse part number 0481010 Bussman Fast Ac...

Page 9: ...5 14 DC Output Wiring Sizing There are two main considerations for sizing DC wire ampacity and voltage drop Ampacity refers to the safe current carrying level as specified by U S based organizations s...

Page 10: ...rews The bulk DC connection may be used as a battery input or as an unfused bulk output The connections require a terminal lug 1 4 single hole lug with a max tongue width of 0 63 or less Size wires ba...

Page 11: ...e included power harness has two wires for the A feed power only pins 1 2 The DPoE Power Patch Panel supports an optional redundant B feed power option but the terminals and wire leads are not attache...

Page 12: ...with a minimum number of commonly available tools 1 2 flat blade and Phillips head screwdrivers Torque wrench 7 16 socket drive Wire and cable strippers PANDUIT part number CT 100 Wire and cable crimp...

Page 13: ...ng boxes until the chassis wiring is complete Power Plant Mounting and Wiring WARNING Ensure all AC and DC power sources are off and disconnected Mechanical Mounting The DPoE Power System chassis is i...

Page 14: ...wer System User s Guide Issue 1 0 Part Number PN380 IEC320 AC cord Cord Bracket Securing Screw Figure 5 Cord Bracket Figure 6 Chassis Rear View AC Connections 4 40 Screws Figure 7 Securing Cord Bracke...

Page 15: ...C connection requires properly crimped terminal lugs 1 4 single hole lug with a max tongue width of 0 63 or less Terminal lugs such as PANDUIT part number LCA4 14 L for use with 3 or 4 AWG stranded wi...

Page 16: ...lease the latch handle Pull the latch handle until the rectifier clears the rear connector on the chassis then gently slide it out of the rear connector With the latch handle open on the replacement r...

Page 17: ...latched into their respective slots Make sure all power and signal connectors are properly mated Table 8 Troubleshooting Alarm Problem Possible Solution DC OK LED is extinguished This rectifier has s...

Page 18: ...Power System EMS Webpage via IPSetup exe on the CD provided with the chassis DPoEPWRCM only The NIC card will also work with Telnet or SNMP NIC Card Settings The NIC card comes equipped with the follo...

Page 19: ...ature sensing device to use for battery temperature compensation Internal sensor or external temperature probes The controller will autosense when an external probe is attached and automatically adjus...

Page 20: ...t Number PN380 15 Parameter Description Default Setting High temperature alarm release NIC Card only The temperature value at which the controller will release a HIGH TEMP alarm For systems using the...

Reviews: