PANDUIT
®
DPoE
™ Power Patch Panel User Manual
Part Number: PN378E
11
Panel Mounting Procedure
WARNING:
Only trained and qualified service personnel should install or service
DPoE
™ Power
Patch Panels. Before installing or servicing
DPoE
™ Power Patch Panels or
communication wiring, be aware of the hazards with the associated electrical circuitry.
1. Record the MAC address, printed on a
Rack Mounting Instructions
sticker on the back of the unit, by writing it
in the space provided on the included
Installation Worksheet (
PANDUIT
part
number PN377).
2. Slip the Wiring Template Label over the
rows of connectors on the back of the
DPoE
™ Power Patch Panel, making sure
the proper wiring code is facing out and that the writing is not upside down. One side of the label
indicates EIA/TIA 568A wiring, while the other side is EIA/TIA 568B wiring.
3. Using a screw from the US standard thread screw set
Grounding Requirements
denoted by “01881-38 REV 2,” attach the green and
yellow striped grounding strap to the panel via the
unthreaded hole nearest the power connector
. Next,
install the panel into a grounded rack using the
appropriate screw set provided to ensure proper
grounding between the panel and the rack. Finally, attach
the loose end of the grounding strap to the rack within the
same position as the panel.
PANDUIT
Structured Ground Kits for Data Center Rack
Grounding
can be used to properly ground
PANDUIT
®
NetRack Rack Systems and racks from most other manufacturers.
4. Record the rack space position on the Installation Worksheet.
ATTENTION:
Observe precautions for handling electrostatic sensitive electronic devices
when installing this product. Ensure that you are properly grounded with a wrist strap
or equivalent while making connections to the 110 punch down terminals on the rear
of the product.
Never make any connections to the 110 punch down terminals when power is applied
to the product.
WARNING:
The supplied screws are part of a grounding system to ensure that the
DPoE
™
Power Patch Panel is properly grounded to the rack.
USE ONLY THE SUPPLIED SCREWS TO ATTACH THE PANEL TO THE RACK.