ACE02 Electronic Swinghandle with PROX Card
Reader Operating Instructions
visit
www.panduit.com
for latest version of this document
Page 2 of 4
The actuator module of the swinghandle is accessed with a six-position
connector on the rear of the unit, shown below.
Pin
Description
Note
1
V
GND
ground (must be same as proximity reader
module)
2
V
SUPPLY
12 to 24 VDC power supply input (may be
connected to prox reader V
CC
input)
3
N/C
no connect
4
Control Signal
command input (9VDC up to supply
voltage, 100 milliseconds minimum)
5
Electronic Lock
Status
open collector output (rated for V
SUPPLY
,
100mA max. load)
6
Mechanical Lock
Status
open collector output (rated for V
SUPPLY
,
100mA max. load)
The proximity reader module of the swinghandle is accessed with a four-
position connector attached to a harness connected to the module’s circuit
board. The module’s connector pinout is:
Pin
Wire Color
Description
Note
1
Black
GND
ground (must be same as
actuator module)
2
Red
VCC
12 to 24VDC power supply input
(may be connected to EML
V
SUPPLY
input)
3
Green
DATA0
DATA0 output
4
White
DATA1
DATA1 output
NOTE:
The mating connectors/harnesses are not provided with the
ACE02. Refer to spec sheet for mating connector/harness requirements.
Control Input Signal
This signal is used to control the electronic lock slide position.
•
for UNLOCKED position: Supply 9VDC minimum (do not exceed
supply voltage) for at least 100 milliseconds. The lock will
remain unlocked for as long as the signal is present, or a
minimum of 3 seconds. Signal timing can typically be adjusted
at the access control device. The control signal current draw is
less than 10mA.
•
for LOCKED position: Supply an open contact or 0VDC (0 to
0.5V)
Electronic Lock Status Output and Mechanical Lock Status Output
Signals
Electronic Lock Status Output Signal
This output will be LOW (GND) when the lock slide is electromechanically
moved to the unlocked position. It will be in the open collector state (high-
impedance) when in the locked position.
Mechanical Lock Status Output Signal
This output will be LOW (GND) when the handle is in the open position or
when the keylock in the actuator is manually unlocked. It will be in the
open collector state (high-impedance) when in the secured position.
NOTE:
These outputs are open collector outputs rated for V
SUPPLY
with
a maximum load of 100mA. To avoid damage to the ACE02, do not
exceed voltage and current ratings.
Status LED and Output Signals
The latch is equipped with a tri-color (blue/magenta/red) LED visible from
the front of the latch. This LED provides a visible notification of the latch
status. The different latch states are described below. Please refer to the
Control Input Signal
,
Electronic Lock Status Output Signal
, and
Mechanical Lock Status Output Signal
sections for further details on
these signals.
Secured
The latch is securely closed, prohibiting access.
•
The Status LED will be solid blue.
•
The electronic lock status output is at its open collector state.
•
The mechanical lock status output is at its open collector state.
“Secured” State
electronic lock
slide in locked
position
handle secured
in housing, cam
in locked
position