background image

ACE02 Electronic Swinghandle with PROX Card 
Reader Operating Instructions 

 

 
visit 

www.panduit.com

 for latest version of this document 

 

 

Page 2 of 4 

The actuator module of the swinghandle is accessed with a six-position 
connector on the rear of the unit, shown below. 
 

 

 
 

Pin 

Description 

Note 

V

GND

 

ground (must be same as proximity reader 
module) 

V

SUPPLY

 

12 to 24 VDC power supply input (may be 
connected to prox reader V

CC

 input) 

N/C 

no connect 

Control Signal 

command input (9VDC up to supply 
voltage, 100 milliseconds minimum) 

Electronic Lock 
Status  

open collector output (rated for V

SUPPLY

100mA max. load) 

Mechanical Lock 
Status 

open collector output (rated for V

SUPPLY

100mA max. load) 

 
 
The proximity reader module of the swinghandle is accessed with a four-
position connector attached to a harness connected to the module’s circuit 
board.  The module’s connector pinout is: 
 

 

 

Pin 

Wire Color 

Description 

Note 

Black 

GND  

ground (must be same as 
actuator module) 

Red 

VCC  

12 to 24VDC power supply input 
(may be connected to EML 
V

SUPPLY

 input) 

Green 

DATA0  

DATA0 output 

White 

DATA1  

DATA1 output 

 
 

 

NOTE:

  The mating connectors/harnesses are not provided with the 

ACE02.  Refer to spec sheet for mating connector/harness requirements. 
 
 

 
Control Input Signal 

 
This signal is used to control the electronic lock slide position.   

 

 

for UNLOCKED position:  Supply 9VDC minimum (do not exceed 
supply voltage) for at least 100 milliseconds.  The lock will 
remain unlocked for as long as the signal is present, or a 
minimum of 3 seconds.  Signal timing can typically be adjusted 
at the access control device.  The control signal current draw is 
less than 10mA. 

 

for LOCKED position: Supply an open contact or 0VDC (0 to 
0.5V) 

 
 
Electronic Lock Status Output and Mechanical Lock Status Output 
Signals 
 
Electronic Lock Status Output Signal 
 

This output will be LOW (GND) when the lock slide is electromechanically 
moved to the unlocked position.  It will be in the open collector state (high-
impedance) when in the locked position.  
 

Mechanical Lock Status Output Signal 
 

This output will be LOW (GND) when the handle is in the open position or 
when the keylock in the actuator is manually unlocked.  It will be in the 
open collector state (high-impedance) when in the secured position. 
 

  

NOTE:

  These outputs are open collector outputs rated for V

SUPPLY

 with 

a maximum load of 100mA.  To avoid damage to the ACE02, do not 
exceed voltage and current ratings.   

 
 
Status LED and Output Signals 
 

The latch is equipped with a tri-color (blue/magenta/red) LED visible from 
the front of the latch.  This LED provides a visible notification of the latch 
status.  The different latch states are described below.  Please refer to the 

Control Input Signal

Electronic Lock Status Output Signal

, and 

Mechanical Lock Status Output Signal

 sections for further details on 

these signals. 
 

Secured

  

 
The latch is securely closed, prohibiting access. 

 

The Status LED will be solid blue. 

 

The electronic lock status output is at its open collector state.   

 

The mechanical lock status output is at its open collector state.   

 

 

“Secured” State 

 

electronic lock 
slide in locked 
position 

handle secured 
in housing, cam 
in locked 
position 