background image

ACE02 Electronic Swinghandle with PROX Card 
Reader Operating Instructions 

 

 
visit 

www.panduit.com

 for latest version of this document 

 

 

Page 3 of 4 

 
Electronically Released 
 

The electronic lock slide is in the unlocked position and the handle can be 
pulled open. 

 

The Status LED will alternate flashing blue/magenta. 

 

The electronic lock status output is 0V while the lock slide is in 
the unlocked position. 

 

The mechanical lock status output is at its open collector state.   

 

 

“Electronically Released” State 

 

Mechanically Released 
 

The latch is released by opening the handle or moving the cam from its 
lock position.     

 

The Status LED will flash blue. 

 

The electronic lock status output will be at its open collector state 
if the electronic lock slide is in the locked position.  It will be 0V if 
the lock slide is in the unlocked position.   

 

The mechanical lock status output is 0V. 

 

  

NOTE:

  The lock sensor is an optical device that senses the presence 

of the lock pawl.  Reflectivity of the lock pawl material can affect sensing.  
Use only approved locks.   
 
 

 

 

“Mechanically Released” State 

 

 
Handle not Fully Closed  
 

This is an interim state and may occur while closing the handle when the 
cam is not secured by the electronic lock slide.  The latch is not fully 
secured during this state. 

 

The Status LED will alternate flashing blue/red if the cam is not 
detected.  It will flash blue/red/red if the cam is detected, but the 
lock plate is not in the right position.  This could be due to 
mechanical failure or tampering. 

 

The electronic lock status output is 0V if the lock slide is in the 
unlocked position.  It will be at its open collector state if it is in the 
lock position. 

 

The mechanical lock status output is 0V if the cam is not 
detected.  It will be at its open collector state if it is detected.  

 

 

 

“Handle not Fully Closed” State 

 

Electronic Lock Slide Error 
 

The electronic lock slide does not respond to the command input signal.   

 

The Status LED will flash magenta if the latch is secured.  It will 
alternate flashing red/magenta if the latch is mechanically 
released. 

 

The electronic lock status output is at its open collector state. 

 

The mechanical lock status output will be at its open collector 
state if the cam is in its lock position.  It will be 0V if the 
mechanical key is moved from its lock position. 

 
 

Error Input Command Sequence 
 

The ACE02 can accept an input command from an external controller to 
flash the status LED red three times.  This feature can be used to indicate 
that an error event has occurred (e.g. unauthorized access attempt).   
 
The control input signal needs to meet the timing requirements shown 
below to flash the status LED red. 

 

 
 

 

T

on

= 5ms

T

on

T

off

= 5ms

T

off

T

burst

T

burst

= 400ms (min)

control 

input

electronic 
lock slide in 
unlocked 
position 

handle 
secured in 
housing, cam 
in locked 
position 

electronic 

lock slide in 

unlocked 

position 

electronic 

lock slide in 

locked 

position 

lock plug in 

unlocked 

position 

cam  

detected by 

latch 

cam not 

detected by 

latch 