44
To determine if outdoor PCB or indoor PCB is faulty:
1. Start with outdoor terminal first.
2. Remove terminal 3 wire.
3. Measure with a multimeter (voltage in DC range).
4. If it is never constant, outdoor PCB is good fluctuating in between 20-70Vdc, outdoor PCB is in good condition.
16.5.2.
Indoor Water Outlet Temperature Sensor Abnormality (H14)
Malfunction Decision Conditions:
During startup and operation of heating, the temperatures detected by the indoor water outlet temperature sensor are used to
determine sensor error.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty sensor.
3. Faulty PCB.
Abnormality Judgment:
Continue for 5 seconds.
Summary of Contents for WH-UD28AE
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 4 1 2 Main Components 4 2 Outdoor Unit ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 23: ...23 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 68: ...68 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 69: ...69 17 5 To Remove Electronic Controller Board and Transformer 17 6 To Remove RCCB ...
Page 71: ...71 When reinstall the water pipe use grease or water at the joining ...
Page 79: ...79 19 2 WH UD24AE WH UD28AE ...
Page 80: ...80 ...