35
13.1.7.
Low Frequency Protection Control 2
• When all the below conditions comply, the compressor frequency will change to lower frequency.
13.1.8.
Low pressure sensor control
• Purpose:
- To protect the system operation.
• Detection period:
- After compressor on for 5 minutes.
• Detection conditions:
- When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
• After detection:
- When abnormality is detected continue 5 seconds, unit stop operation.
- Error H63 will be displayed.
13.1.9.
High pressure sensor control
• Purpose:
- To protect the system operation.
• Detection period:
- After compressor on for 5 minutes.
• Detection conditions:
- When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
• After detection:
- When abnormality is detected continue 5 seconds, unit stop operation.
- Error H64 will be displayed.
13.2. Protection Control For Heating Operation
13.2.1.
Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14
°
C in order to avoid compressor
overloading.
13.2.2.
Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
13.2.3.
Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor stop.
Temperature, T, for:
Heating
Outlet water (
°
C)
T < 14 or T 48
Outdoor air (
°
C)
T < 4 or T 24
Indoor heat exchanger (
°
C)
T
0
Summary of Contents for WH-UD28AE
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 4 1 2 Main Components 4 2 Outdoor Unit ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 23: ...23 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 68: ...68 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 69: ...69 17 5 To Remove Electronic Controller Board and Transformer 17 6 To Remove RCCB ...
Page 71: ...71 When reinstall the water pipe use grease or water at the joining ...
Page 79: ...79 19 2 WH UD24AE WH UD28AE ...
Page 80: ...80 ...