4. Features
Inverter Technology
- Energy saving
High Efficiency
Compact Design
Environment Protection
- Non-ozone depletion substances refrigerant (R32)
Easy to use control panel
Weekly Timer setting
Quality Improvement
- Random auto restart after power failure for safety restart operation
- Gas leakage protection
- Prevent compressor reverse cycle
- Inner protector to protect compressor
Serviceability Improvement
- Breakdown Self Diagnosis function
- System Status Check Buttons for servicing purpose
- System Pumpdown Button for servicing purpose
- Front maintenance design for outdoor unit
Operation Condition
HEATING (CIRCUIT)
*1*2
COOLING (CIRCUIT)
Water outlet temperature (°C)
(Min. / Max)
20 / 55 (Below Ambient -20°C)
*3
20 / 60 (Ambient -15 ~ 0°C or
Above Ambient 25°C) *³
20 / 65 (Ambient 5 ~ 20°C)
*3*4
5 / 20
Outdoor ambient temperature (°C)
(Min. / Max)
-20 / 35
10 / 43
NOTICE : When the outdoor temperature is out of the above temperature range, the heating capacity will drop significantly and
outdoor unit might stop for protection control.
*3
Between outdoor ambient -15°C and -20°C, the water outlet temperature gradually decreases from 60°C to 55°C.
*3
Between outdoor ambient 5°C and 0°C, the water outlet temperature gradually decreases from 65°C to 60°C.
*3
Between outdoor ambient 20°C and 25°C, the water outlet temperature gradually decreases from 65°C to 60°C.
*4
Only when ΔT is set to 15°C, the set temperature above 60°C will take effect.