 WARNING 

18. 

This equipment is strongly recommended to be installed with Residual Current Device (RCD) on-site according to the respective 
national wiring rules or country-specific safety measures in terms of residual current. 

 

19. 

The unit is only for use in a closed water system. Utilization in an open water system may lead to excessive corrosion of the water 
piping and risk of incubating bacteria colonies, particularly Legionella, in water. 

 

20.  If there is any doubt about the installation procedure or operation, always contact the authorized dealer for advice and information. 

 

21.  Select a location where in case of water leakage, the leakage will not cause damage to other properties. 

 

22. 

When installing electrical equipment at wooden building of metal lath or wire lath, in accordance with electrical facility standard, no 
electrical contact between equipment and building is allowed. Insulator must be installed in between. 

 

23. 

This installation may be subjected to building regulation approval applicable to respective country that may require to notify the local 
authority before installation. 

 

24. 

Any work carried out on the Mono bloc unit after removing the front panel which is secured by screws, must be carried out under the 
supervision of authorized dealer and licensed installation contractor. 

 

25. 

This unit must be properly earthed, the electrical earth must not be connected to a gas pipe, water pipe, the earth of a lightning rod or 
a telephone. Otherwise there is a danger of electrical shock in the event of an insulation breakdown or electrical earth fault in the 
Mono bloc unit. 

 

 

 CAUTION 

1. 

Do not install the Mono bloc unit in areas where there is a risk of flammable gas leakage. There is a risk of fire if flammable gas 
accumulates near or around the Mono bloc unit. 

 

2. 

Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the 
liquid refrigerant, it may cause frostbite. 

 

3. 

Make sure the power supply cord does not contact with hot part (i.e. water piping). High temperature may cause insulator of power 
supply cord damage hence electrical shock or fire. 

 

4. 

Do not touch the sharp aluminum fins or edges of metal parts. 
If you are required to handle sharp parts during installation or servicing, please wear hand glove. 
Sharp parts may cause injury.  

 

 

5. 

Do not apply excessive force to water pipes that may damage the pipes. If water leakage occurs, it will cause flooding and damage to 
other properties. 

 

6. 

Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water leakage may happen and may 
cause damage to properties of the user. 

 

7. 

The piping installation work must be flushed before the Mono bloc unit is connected to remove contaminants. Contaminants may 
damage the Mono bloc unit components. 

 

8.  Select an installation location where it is accessible for maintenance. 

 

9. 

Power supply connection to the Mono bloc unit. 

 

Power supply point should be in easily accessible place for power disconnection in case of emergency. 

 

Must follow local national wiring standard, regulation and this installation instruction. 

 

Strongly recommended to make permanent connection to a circuit breaker. It must be a double pole switch with a minimum 
3.0 mm gap. 

Power supply 1: Use approved 40A circuit breaker 

Power supply 2: Use approved 40A circuit breaker 

 

10.  Ensure the correct polarity is maintained throughout all wiring. Otherwise, it will cause electrical shock or fire. 

 

11. 

After installation, the installer is obliged to verify correct operation of the Mono bloc unit. Check the connection point for water leakage 
during test run. If leakage occurs, it will cause damage to other properties. 

 

12. 

Installation work. 
Four or more people are required to carry out the installation work. The weight of Mono bloc unit might cause injury if carried by less 
than four people. 

 

 
 
 
 
 
 
 
 

Summary of Contents for WH-MHF12G6E5

Page 1: ...cians technical individ epaired only by is service infor TION OF LOW gerant leakage ETY NOTIC rtant for safety arts List It is es zards Do not NG s only and is n duals of potent y experienced rmation by anyo TEMPERATU during the inst CE These parts a ssential that the modify the orig ot designed for tial dangers in professional te one else could RE tallation or repa Panaso Order No Mono WH M WH M ...

Page 2: ...not tie up the power supply cord into a bundle by band Abnormal temperature rise on power supply cord may happen 4 Do not insert your fingers or other objects into the unit high speed rotating fan may cause injury 5 Do not sit or step on the unit you may fall down accidentally 6 Keep plastic bag packaging material away from small children it may cause suffocation 7 Do not use pipe wrench to instal...

Page 3: ...stallation re installation and during repairing a refrigeration parts Take care of the liquid refrigerant it may cause frostbite 3 Make sure the power supply cord does not contact with hot part i e water piping High temperature may cause insulator of power supply cord damage hence electrical shock or fire 4 Do not touch the sharp aluminum fins or edges of metal parts If you are required to handle ...

Page 4: ...0 Top Fan 550 Bottom Fan Heat Exchanger Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 51 18 Size W H L mm 903 7 1295 4 38 1 Item Unit Mono Bloc Unit Dimension Height mm inch 1410 55 1 2 Width mm inch 1283 50 1 2 Depth mm inch 320 12 19 32 Net Weight kg lbs 151 333 Noise Level dB A 50 Power Level dB 67 Power Source Phase Voltage Cycle ø Single V 230 Hz 50 Input Power kW 2 ...

Page 5: ...tor No of Speed 7 Software Selection Input Power W 72 Hot Water Coil Type Brazed Plate No of Plates 80 Size W x H x L mm 130 93 325 Water Flow Rate l min m 3 h 34 4 2 1 Pressure Relief Valve Water Circuit kPa Open 300 Close 265 and below Flow Switch Magnetic Lead Switch Protection Device A Residual Current Circuit Breaker 40 Expansion Vessel Volume I 10 MWP bar 3 Capacity of Integrated Electric He...

Page 6: ...everse cycle Inner protector to protect compressor Serviceability Improvement Breakdown Self Diagnosis function System Status Check Buttons for servicing purpose System Service Mode Button for servicing purpose Front maintenance design for mono bloc unit Operation Condition Water outlet temperature C Ambient temperature C HEATING Maximum 65 35 Minimum 25 20 NOTICE When the outdoor temperature is o...

Page 7: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit Air inlet rear Air outlet Air inlet side Handle 2 pieces front and 2 pieces behind Cabinet Front Plate Top Plate ...

Page 8: ... Pump Station cable 2 x min 0 5mm2 Component name 1 PCB 2 Pressure relief valve 3 Flow switch 4 Pressure gauge 5 Water pump 6 RCCB 7 Bushing 8 Cabinet front plate 9 Cabinet top plate 0 Overload protector a Heater assembly b Expansion vessel c Cover d Air purge valve Connector name g Water inlet h Water outlet VIEW WITHOUT COVER DETAIL Ag DETAIL Ah FOR WH MHF12G6E5 WITHOUT OLP COVER FOR WH MHF09G3E...

Page 9: ...20 5 Dimensions 5 1 Mono Bloc Unit 579 400 356 154 1410 615 426 5 175 275 413 30 c c 70 277 320 152 1283 256 30 293 318 5 50 45 45 45 83 5 Unit mm Top View Front View Back View Side View Side View ...

Page 10: ... Pressure Relief Valve Air Purge Valve Water Flow Switch Water Pump Water Inlet Connect to Sanitary Tank Water Outlet Connect to Sanitary Tank Drain Refrigerant Cycle Water Cycle Heat Exchanger Heat Exchanger Strainer Strainer Subcooler 4 Way Valve Gas Side 3 Way Valve Liquid Side 3 Way Valve Pressure Switch High Pressure Sensor Compressor Discharge Temp Sensor Compressor Water Pressure Gauge Capi...

Page 11: ... L3 BLK AC2 N2 WHT SURGE PROTECTION CIRCUIT SIGNAL DETECTION CIRCUIT ACN BOOSTER WHT t 80 3 C CN OLP1 WHT 2 1 B B TERMINAL BOARD REFRIGERANT SYSTEM BACKUP HEATER O R 80 3 C O OLP 80 3 C BL R BL BL BL W BL W L1 N1 W GROUNDING TERMINAL BOARD ELCB T3 Y G G 3 1 1 1 BL BL 2 2 CN HT WHT O 1 1 2 2 3 3 2 2 1 1 A B SIGNAL DETECTION CIRCUIT R BR O BL Y R BR O BL Y CONTROL PANEL SURGE PROTECTION CIRCUIT GRN ...

Page 12: ...HIT E B L CAPACITOR ELECTRONIC CONTROLLER A C C B LA CK B 1 CN ACL A C B LK 01 O P TIONA L 4 REA CTO R W G R W RE LA Y 6 W RY HOT FG 2 GREE N BL BL BL DCN OUT ELECTRONIC CONTROLLER SUB CN AC N BLAC K FG 1 G REE N WHITE B LA CK A C B LK CN B LK B LA CK CN W HT CIRCUIT W R B B Y R BR Y W HIT E HEA T E R CIRCUIT W HITE CIRCUIT R LOW PRESSURE SENSOR HIGH PRESSURE SENSOR 2 3 1 BL 4 CN LPS BLUE CN HOT B...

Page 13: ...FORCE button In AIR PURGE function the pump will operate ON and OFF for 10 minutes to purge the air in the hydraulic system Press again the FORCE button to exit AIR PURGE function PUMP SPEED ADJUST MODE will stop operation 14 5 Expansion Vessel Pre Pressure Checking Expansion Vessel with 10 L air capacity and initial pressure of 1 bar is installed in this Mono bloc unit Total amount of water in sy...

Page 14: ...r air temperature 7 C DBT 6 C WBT o Indoor water inlet temperature 30 C o Indoor water outlet temperature 35 C Outdoor Temperature C Outdoor Temperature C Input Power kW 15 12 9 6 3 0 3 6 9 12 9 000 10 000 11 000 12 000 13 000 14 000 Capacity kW 1 500 2 500 3 500 4 500 5 500 6 500 15 12 9 6 3 0 3 6 9 12 ...

Page 15: ...000 1520 9000 1700 9000 1880 9000 2160 9000 2630 9000 3200 is tested with dT 8 C is tested with dT 10 C 18 2 2 WH MHF12G6E5 Water Out C 30 35 40 45 55 65 Outdoor Air C Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W 15 12000 5160 12000 5530 11000 5510 10800 5490 9700 5520 8000 5610 7 12000 4430 12...

Reviews: