1. Safety Precautions 

  Read the following “SAFETY PRECAUTIONS” carefully before installation of (Mono bloc) Air-to-Water Heatpump 

system (hereafter referred to as “Mono bloc unit”). 

  Electrical works and water installation works must be done by licensed electrician and licensed water system 

installer respectively. Be sure to use the correct rating and main circuit for the model to be installed. 

  The caution items stated here must be followed because these important contents are related to safety. The 

meaning of each indication used is as below. Incorrect installation due to ignorance or negligence of the 
instructions will cause harm or damage, and the seriousness is classified by the following indications. 

 

 WARNING 

This indication shows the possibility of causing death or serious injury. 

 CAUTION

 

This indication shows the possibility of causing injury or damage to properties only. 

 

 

The items to be followed are classified by the symbols: 

 

 

This symbol denotes item that is PROHIBITED from doing. 

 

Symbol with dark background denotes item that must be carried out. 

 

 

Carry out test run to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and 
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference. 

 

If there is any doubt about the installation procedure or operation, always contact the authorized dealer for advice and 
information. 

 

 WARNING 

1. 

Do not install Mono bloc unit near handrail of veranda. When installing Mono bloc unit at veranda of high rise building, child may climb 
up to Mono bloc unit and cross over the handrail and causing accident. 

 

2. 

Do not use unspecified cord, modified cord, join cord or extension cord for power supply cord. Do not share the single outlet with other 
electrical appliances. 
Poor contact, poor insulation or over current will cause electrical shock or fire. 

 

3.  Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen. 

 

4.  Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.  

 

 

5.  Do not sit or step on the unit, you may fall down accidentally. 

 

 

6.  Keep plastic bag (packaging material) away from small children, it may cause suffocation. 

 

7.  Do not use pipe wrench to install refrigerant pipe. It might deform the piping and cause the unit to malfunction. 

 

8.  Do not purchase unauthorized electrical parts for installation, service, maintenance and etc.. They might cause electrical shock or fire.

 

9.  This unit is a multi supply appliances. All circuits must be disconnected before accessing to the unit terminals. 

 

10. 

Do not modify the wiring of Mono bloc unit for installation of other components (i.e. heater, etc.). Overloaded wiring or wire connection 
points may cause electrical shock or fire. 

 

11.  Do not add or replace refrigerant other than specified type. It may cause product damage, burst and injury etc. 

 

12. 

For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and 
single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or 
fire. 

 

13. 

For water circuit installation work, follow to relevant European and national regulations (including EN61770) and local plumbing and 
building regulation codes. 

 

14. 

Must engage an authorized dealer or specialist for installation. If installation is defective, it will cause water leakage, electrical shock or 
fire. 

 

15.  Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fire. 

 

16. 

Only use the supplied or specified installation parts. Else, it may causes Mono bloc unit vibrate, fall, water leakage, electrical shock or 
fire. 

 

17. 

Install at a flat, strong and firm location which is able to withstand the Mono bloc unit’s weight. If the location is slanting, or strength is 
not enough the set will fall and cause injury. 

 

Summary of Contents for WH-MHF12G6E5

Page 1: ...cians technical individ epaired only by is service infor TION OF LOW gerant leakage ETY NOTIC rtant for safety arts List It is es zards Do not NG s only and is n duals of potent y experienced rmation by anyo TEMPERATU during the inst CE These parts a ssential that the modify the orig ot designed for tial dangers in professional te one else could RE tallation or repa Panaso Order No Mono WH M WH M ...

Page 2: ...not tie up the power supply cord into a bundle by band Abnormal temperature rise on power supply cord may happen 4 Do not insert your fingers or other objects into the unit high speed rotating fan may cause injury 5 Do not sit or step on the unit you may fall down accidentally 6 Keep plastic bag packaging material away from small children it may cause suffocation 7 Do not use pipe wrench to instal...

Page 3: ...stallation re installation and during repairing a refrigeration parts Take care of the liquid refrigerant it may cause frostbite 3 Make sure the power supply cord does not contact with hot part i e water piping High temperature may cause insulator of power supply cord damage hence electrical shock or fire 4 Do not touch the sharp aluminum fins or edges of metal parts If you are required to handle ...

Page 4: ...0 Top Fan 550 Bottom Fan Heat Exchanger Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 51 18 Size W H L mm 903 7 1295 4 38 1 Item Unit Mono Bloc Unit Dimension Height mm inch 1410 55 1 2 Width mm inch 1283 50 1 2 Depth mm inch 320 12 19 32 Net Weight kg lbs 151 333 Noise Level dB A 50 Power Level dB 67 Power Source Phase Voltage Cycle ø Single V 230 Hz 50 Input Power kW 2 ...

Page 5: ...tor No of Speed 7 Software Selection Input Power W 72 Hot Water Coil Type Brazed Plate No of Plates 80 Size W x H x L mm 130 93 325 Water Flow Rate l min m 3 h 34 4 2 1 Pressure Relief Valve Water Circuit kPa Open 300 Close 265 and below Flow Switch Magnetic Lead Switch Protection Device A Residual Current Circuit Breaker 40 Expansion Vessel Volume I 10 MWP bar 3 Capacity of Integrated Electric He...

Page 6: ...everse cycle Inner protector to protect compressor Serviceability Improvement Breakdown Self Diagnosis function System Status Check Buttons for servicing purpose System Service Mode Button for servicing purpose Front maintenance design for mono bloc unit Operation Condition Water outlet temperature C Ambient temperature C HEATING Maximum 65 35 Minimum 25 20 NOTICE When the outdoor temperature is o...

Page 7: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit Air inlet rear Air outlet Air inlet side Handle 2 pieces front and 2 pieces behind Cabinet Front Plate Top Plate ...

Page 8: ... Pump Station cable 2 x min 0 5mm2 Component name 1 PCB 2 Pressure relief valve 3 Flow switch 4 Pressure gauge 5 Water pump 6 RCCB 7 Bushing 8 Cabinet front plate 9 Cabinet top plate 0 Overload protector a Heater assembly b Expansion vessel c Cover d Air purge valve Connector name g Water inlet h Water outlet VIEW WITHOUT COVER DETAIL Ag DETAIL Ah FOR WH MHF12G6E5 WITHOUT OLP COVER FOR WH MHF09G3E...

Page 9: ...20 5 Dimensions 5 1 Mono Bloc Unit 579 400 356 154 1410 615 426 5 175 275 413 30 c c 70 277 320 152 1283 256 30 293 318 5 50 45 45 45 83 5 Unit mm Top View Front View Back View Side View Side View ...

Page 10: ... Pressure Relief Valve Air Purge Valve Water Flow Switch Water Pump Water Inlet Connect to Sanitary Tank Water Outlet Connect to Sanitary Tank Drain Refrigerant Cycle Water Cycle Heat Exchanger Heat Exchanger Strainer Strainer Subcooler 4 Way Valve Gas Side 3 Way Valve Liquid Side 3 Way Valve Pressure Switch High Pressure Sensor Compressor Discharge Temp Sensor Compressor Water Pressure Gauge Capi...

Page 11: ... L3 BLK AC2 N2 WHT SURGE PROTECTION CIRCUIT SIGNAL DETECTION CIRCUIT ACN BOOSTER WHT t 80 3 C CN OLP1 WHT 2 1 B B TERMINAL BOARD REFRIGERANT SYSTEM BACKUP HEATER O R 80 3 C O OLP 80 3 C BL R BL BL BL W BL W L1 N1 W GROUNDING TERMINAL BOARD ELCB T3 Y G G 3 1 1 1 BL BL 2 2 CN HT WHT O 1 1 2 2 3 3 2 2 1 1 A B SIGNAL DETECTION CIRCUIT R BR O BL Y R BR O BL Y CONTROL PANEL SURGE PROTECTION CIRCUIT GRN ...

Page 12: ...HIT E B L CAPACITOR ELECTRONIC CONTROLLER A C C B LA CK B 1 CN ACL A C B LK 01 O P TIONA L 4 REA CTO R W G R W RE LA Y 6 W RY HOT FG 2 GREE N BL BL BL DCN OUT ELECTRONIC CONTROLLER SUB CN AC N BLAC K FG 1 G REE N WHITE B LA CK A C B LK CN B LK B LA CK CN W HT CIRCUIT W R B B Y R BR Y W HIT E HEA T E R CIRCUIT W HITE CIRCUIT R LOW PRESSURE SENSOR HIGH PRESSURE SENSOR 2 3 1 BL 4 CN LPS BLUE CN HOT B...

Page 13: ...FORCE button In AIR PURGE function the pump will operate ON and OFF for 10 minutes to purge the air in the hydraulic system Press again the FORCE button to exit AIR PURGE function PUMP SPEED ADJUST MODE will stop operation 14 5 Expansion Vessel Pre Pressure Checking Expansion Vessel with 10 L air capacity and initial pressure of 1 bar is installed in this Mono bloc unit Total amount of water in sy...

Page 14: ...r air temperature 7 C DBT 6 C WBT o Indoor water inlet temperature 30 C o Indoor water outlet temperature 35 C Outdoor Temperature C Outdoor Temperature C Input Power kW 15 12 9 6 3 0 3 6 9 12 9 000 10 000 11 000 12 000 13 000 14 000 Capacity kW 1 500 2 500 3 500 4 500 5 500 6 500 15 12 9 6 3 0 3 6 9 12 ...

Page 15: ...000 1520 9000 1700 9000 1880 9000 2160 9000 2630 9000 3200 is tested with dT 8 C is tested with dT 10 C 18 2 2 WH MHF12G6E5 Water Out C 30 35 40 45 55 65 Outdoor Air C Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W 15 12000 5160 12000 5530 11000 5510 10800 5490 9700 5520 8000 5610 7 12000 4430 12...

Reviews: