111
16.5.23
Output Over Current Detection (F23)
Malfunction Decision Conditions:
During operation of cooling and heating, when outdoor DC current is above 39.0 ± 5.0 A is detected by the IPM
DC Peak sensing circuitry in the outdoor unit PCB (main).
Malfunction Caused:
1 Faulty outdoor unit PCB (main).
2 Faulty
compressor.
Abnormality Judgment:
Continue for 7 times.