Indoor Freeze-up Protection (H99)
Malfunction Decision Conditions:
During anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0°C.
Malfunction Caused:
1 Faulty
water
pump.
2 Insufficient water flow rate in system.
3 Water leak in system.
4 2 way valve partially closed.
5 Clogged expansion valve or strainer.
6 Refrigerant shortage (refrigerant leakage).
7 Faulty indoor refrigerant liquid temperature sensor.
8 Faulty indoor unit PCB (main).