iii
When Connecting Refrigerant
Tubing
Pay particular attention to refrigerant
leakages.
WARNING
•
When performing piping work,
do not mix air except for
specified refrigerant (R410A)
in refrigeration cycle. It causes
capacity down, and risk of
explosion and injury due to high
tension inside the refrigerant
cycle.
•
If the refrigerant comes in contact
with a flame, it produces a toxic
gas.
•
Do not add or replace refrigerant
other than specified type. It may
cause product damage, burst and
injury, etc.
•
Ventilate the room immediately, in the
event that is refrigerant gas leaks during
the installation. Be careful not to allow
contact of the refrigerant gas with a
flame as this will cause the generation
of toxic gas.
•
Keep all tubing runs as short as
possible.
•
Apply refrigerant lubricant to the
matching surfaces of the flare and union
tubes before connecting them, then
tighten the nut with a torque wrench for
a leak-free connection.
•
Check carefully for leaks before starting
the test run.
•
Do not leak refrigerant while piping work
for an installation or re-installation, and
while repairing refrigeration parts.
Handle liquid refrigerant carefully as it
may cause frostbite.
When Transporting
Be careful when picking up and moving
the indoor and outdoor units. Get a
It may need two or more people to carry
out the installation work.
partner to help, and bend your knees
when lifting to reduce strain on your back.
Sharp edges or thin aluminum fins on the
air conditioner can cut your fingers.
When Installing…
Select an installation location which is
rigid and strong enough to support or
hold the unit, and select a location for
easy maintenance.
…In a Room
Properly insulate any tubing run inside
a room to prevent “sweating” that can
cause dripping and water damage to
walls and floors.
CAUTION
Keep the fire alarm and
the air outlet at least
1.5 m away from the unit.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete
blocks to provide a solid, level foundation
for the outdoor unit. This prevents water
damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down
with bolts and a metal frame. Provide a
suitable air baffle.
…In a Snowy Area (for Heat Pump-
type Systems)
Install the outdoor unit on a raised
platform that is higher than drifting snow.
Provide snow vents.
00_271537_2WAY_Eng.indb 3
2015-9-10 16:14:54
•
•
When Servicing
•
Turn
the power OFF at the main
power box (mains), wait at least 10
minutes until it is discharged, then
open the unit to check or repair
electrical parts and wiring.
•
K
eep your fingers and clothing away from
any moving parts.
• Clean up the site after you finish,
remembering to check that no metal
scraps or bits of wiring have been left
inside the unit.
WARNING
• This product must not be
modified or disassembled under
any circumstances. Modified or
disassembled unit may cause fire,
electric shock or injury.
• Do not clean inside the indoor and
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
• In case of malfunction of this
appliance, do not repair by yourself.
Contact to the sales dealer or
service dealer for a repair.
CAUTION
•
V
entilate any enclosed areas when
installing or testing the refrigeration
system. Leaked refrigerant gas,
on contact with fire or heat, can
produce dangerously toxic gas.
• Confirm after installation that no
refrigerant gas is leaking. If the gas
comes in contact with a bu
r
ning
stove, gas water heater, electric
room heater or other heat source,
it can cause the generation of
gas.
Others
CAUTION
• Do not touch the air inlet or
the sharp aluminum fins of the
outdoor unit. You may get
injured.
• Do not sit or step on the unit,
you may fall down accidentally.
• Do not stick any object into the
FAN CASE.
You may be injured and the unit
may be damaged.
00_271537_2WAY_Eng.indb 4
2015-9-10 16:14:55
SM830253-00_欧州2way7_SM-TRSM.indb 4
16/08/02 13:44:06