2WAY SYSTEM
Control Functions - Outdoor unit
1 - 28
1
8. 4-Way Valve Adjustment Control
8. 4-Way Valve Adjustment Control
2WAY VRF SYSTEM
Control Functions
The first operation after turning on power supply to outdoor unit.
The mode of the system changes.
The purpose of this control is to change over the 4-way valve appropriately with big pressure difference.
This control is performed at the following conditions.
Cooling operation
* When the above operation is finished, normal operation starts at the horsepower determined by the indoor units
where thermostats are ON.
* When the above operation is finished, normal operation starts at the horsepower determined by the indoor units
where thermostats are ON.
The first operation after all outdoor units stopped for 60 minutes.
For 60 seconds
Indoor units
Control time
Outdoor units
MOV
RAP valve kit
Fan
All outdoor units operate at the maximum capacity.
MOV at all indoor units operate at a fixed pulse according to the indoor unit
capacity.
All indoor units operate in Cooling mode (OFF status).
Fan rotates at the set fan speed depending on the indoor unit operation mode
or at fan speed “LL”.
Minimum 1 min - Maximum 20 min [until max. (pressure sensor temp.) 35°C]
Indoor unit
s
Control time
Outdoor units
MOV
RAP valve kit
Fan
All outdoor units operate at the maximum capacity.
MOV at all indoor units operate at 250 pulses.
All indoor units operate in heating mode (ON status).
Fan rotates at the set fan speed depending on the indoor unit operation mode or at
“LL” fan speed, or stops.
Heating operation