Control Functions - Outdoor unit
1
3. Compressor Control
2WAY VRF SYSTEM
Control Functions
3. Compressor Control
PX=58.0
PX=58.0
57.9
55.1
55.0
52.9
Thermostat
OFF
Compressor
capacity
decrease
Compressor
capacity
increase
prohibited
Compressor
capacity
increase
possible
Area D
Area C
Area B
Area A
53.0
°C
°C
・
Standard setting (at factory shipment)
・
Renewal setting (JP06 cut on all outdoor unit PCB)
* For details, see Section 9 of Technical Data.
57.9
50.0
47.9
Thermostat
OFF
Compressor
capacity
decrease
Compressor
capacity
increase
prohibited
Compressor
capacity
increase
possible
Area D
Area C
Area B
Area A
50.1
48.0
50.0
15
30
0
48.0
40.5
34.0
33.0
°C
Max. required level
42.0
PX= 52.5
49.1
47.0
46.9
Thermostat
OFF
Compressor
capacity
decrease
Compressor
capacity
increase
prohibited
Compressor
capacity
increase
prohibited
Compressor
capacity
decrease
Compressor
capacity
increase
prohibited
Compressor
capacity
increase
prohibited
Area D
Area C
Area B
Area A
52.5-0.1
49.0
°C
°C
Thermostat
OFF
Area D
Area C
Area B
Area A
48.0
15
30
0
47.0
39.5
32.5
32.5
°C
Max. required level
40.0
PX= 52.5
48.1
47.0
46.9
52.5-0.1
48.0