2
- 3
2WAY SYSTEM
Control Functions - Indoor Unit
2
1. Room Temperature Control
Remote controller sensor is enabled
Set temp. in remote
controller
28
℃
28
℃
28
℃
Detected temp. by
sensor
30.0
℃
27.5
℃
27.0
℃
Detected temp. by
body sensor
30.0
℃
27.5
℃
27.0
℃
Detected temp. by
remote controller
sensor
30.0
℃
27.5
℃
27.0
℃
Room temp. = temp.
detected by remote
controller sensor
30.0
℃
=30.0
27.5
℃
=27.5
27.0
℃
=27.0
T
+2.0deg -0.5deg -1.0deg
Thermostat
ON
Thermostat
OFF
Thermostat
OFF
Remote controller sensor is enabled
Set temp. in remote
controller
20
℃
20
℃
20
℃
Detected temp. by
sensor
17.0
℃
20.5
℃
21.0
℃
Detected temp. by
body sensor
21.0
℃
24.5
℃
25.0
℃
Detected temp. by
remote controller
sensor
17.0
℃
20.5
℃
21.0
℃
Room temp. = temp.
detected by remote
controller sensor
17.0
℃
=17.0
20.5
℃
=20.5
21.0
℃
=21.0
T
+3.0deg -0.5deg -1.0deg
Thermostat
ON
Thermostat
OFF
Thermostat
OFF
①
The thermostat does not turn OFF for 3 minutes after it turns ON.
②
The thermostat does not turn ON for 1 to 3 minutes after it turns OFF.
③
The thermostat does not turn OFF for 60 minutes during the test run mode. (Forced thermostat ON)
*However, the thermostat turns OFF if an alarm occurs.
ON
ON
OFF
Set temp.
Set temp.
Set temp.
Set temp.
-1
+1
+2
(deg)
ON
ON
OFF
+1
+2
-1
(deg)
ON
ON
OFF
-1
+1
+2
(deg)
Heating
ON
ON
OFF
+1
+2
-1
(deg)
Body sensor is enabled
Remote controller sensor is enabled
-0.5
-0.5
Room temp.
Cooling
Room temp.
Cooling
Heating
Room temp.
Room temp.
Thermostat
Thermostat
Thermostat
Thermostat
SM830204-05_2WAY SYS.indb 3
2015/01/21 17:00:33