2WAY SYSTEM
Outdoor Unit Maintenance Remote Controller
4
- 12
4
6. Mode Settings
2WAY SYSTEM
Outdoor Unit Maintenance Remote Controller
6. Mode Settings
Setting mode 1
<Operating procedure>
Press and hold the
1
2
(CHECK) button and
(VENTILATION) button simultaneously for 4
seconds or longer.
Press the temperature setting
and
buttons to change the item code. The item codes
and setting data are shown in the table of “List of
Item Codes” on the next page.
Press the timer time
and
buttons to
change the setting data.
To confirm the changed setting data, press the
button.
(At this time, “ ” display stops blinking
and remains lit.)
During this mode, “ ” is displayed,
blinking. The outdoor unit address display section
displays “ALL,” the item code and number (DN
value in the table), and the setting data (6 digits).
(The setting data is displayed in 6 digits. The
display changes between the first 3 digits (Fig. A )
and the last 3 digits (Fig. B
B
B
A
A
).
When the first 3 digits are displayed, the bottom dot
of the colon is illuminated.)
To exit the setting mode, press the
(CHECK)
button.
1
2
3
5
5
3
1
2
and
are displayed alternately.
(Example shows display of 000 001.)
Display of fi rst 3 digits
Display of last 3 digits
Description
Parameter
DN
Snowfall sensor usage
000 = Sensor input not present. Control is performed.
001 = Sensor input present. Control is performed.
002 = Sensor input not present. Control is not performed.
003 = Sensor input present. Control is not performed.
Outdoor unit fan Quiet
mode
000 = Disabled
002 = Quiet mode 2
001 = Quiet mode 1
003 = Quiet mode 3
004 = Quiet mode 4 ... 012 = Quiet mode 12
Energy saving mode
000 = None
001 = Discharge temp. control only (Mode 3)
002 = Demand only (Mode 2)
003 = Discharge temp. c Demand (Mode 1)
Energy saving operation
plug
000 = Independent
001 = All indoor units linked
Demand 1 current
Demand 2 current
High static pressure mode
000 = Disabled
001 = High static pressure mode
* Charge when the external static pressure is increased to over 30 Pa.
3
4
5
130 = 130% ... -001 = no limit
000 = 0%
040 = 40% ...
070 = 70% ...
100 = 100% ...
000 = 0%
040 = 40% ...
070 = 70% ...
100 = 100% ...
130 = 130% ... -001 = no limit
SM830204-05_2WAY SYS.indb 12
2015/01/23 11:57:00
Summary of Contents for U-20ME1E81
Page 54: ... MEMO 1 46 ...
Page 102: ... MEMO 3 36 ...
Page 116: ... MEMO 4 14 ...
Page 177: ...201502 ...