1-15
1
1
Outdoor Units U-250PE1E8
–
–
–
–
–
–
–
KTM-35D-S1, DTN-C532G3H
CM-12
–
–
–
UKV-25D18
UKV-U030E, DC 12 V
STF-0712G
STF-01AI518A1, AC 220-240 V, 50Hz / 60Hz
MODEL No.
Outdoor Unit
Power Transformer
Rated
VAC, Hz
Source
Secondary
Coil resistance
Ω
Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4
Resistance
kΩ
Thermistor (Discharge gas sensor): TH5
Resistance
kΩ
Relay (Comp. Magnetic Contactor)
VAC
Coil rated
VAC, A
Contact rating
Coil resistance (at 20°C)
Ω
Sol-Control-Valve
4 way valve
4 way valve
Electro magnetic coil
Thermal cut off temperature
Sol-control-valve
Magnetic coil
–10°C: 23.7±5%
20°C:
6.5±5%
–5°C: 18.8±5%
30°C:
4.4±5%
0°C: 15.0±5%
40°C:
3.1±5%
5°C: 12.1±5%
45°C:
2.6±5%
10°C:
9.7±5%
50°C:
2.1±5%
60°C: 12.4±5%
90°C:
4.6±5%
70°C:
8.7±5%
100°C:
3.4±7%
75°C:
7.4±5%
110°C:
2.5±7%
80°C:
6.3±5%
120°C:
1.9±7%
85°C:
5.3±5%
130°C:
1.5±7%
U-250PE1E8
Sec1.indd 15
2014/11/07 10:27:51