Design of 3WAY VRF SYSTEM
2
- 52
1
2
3
4
5
6
7
8
9
8-3-5-4. Procedure
1.
2.
3.
4.
Connect the power supply wire to the solenoid valve kit, using
the Class wire.(Fig. 3)
Connect the solenoid valve kit to the solenoid valve relay kit,
using the Class wire shown in Table 19. (Fig. 2, Fig. 3)
Connect the solenoid valve relay kit to the indoor unit, using
the supplied connecting wire. (Fig. 1, Fig. 2)
The left-over wires connected to the solenoid valve relay kit
should be tied up in a bundle of wires by the supplied wire
holder not to leave the wires loose as shown in the diagram
at right. (Fig. 2)
Ⅰ
Ⅱ
Solenoid valve relay kit
Solenoid valve kit
1 2 3 4 5
Class
3-Way connect wire
(supplied)
Class
Control wire
(field supplied)
* Wiring fixed with clamper
* Wiring fixed
with clamper
Ⅱ
Ⅱ
Fig. 2
Clamper
(supplied)
Clamper
Wire
* Wiring fixed with clamper
Fig. 3
* Wiring fixed
with clamper
Ground
* Wiring fixed
with clamper
Class Power supply
(field supplied)
Ⅰ
Conduit
(field supplied)
Class Control wire
(field supplied)
Ⅱ
How to connect wiring to the terminal
■
For stranded wiring
(1)
(2)
(3)
(4)
Cut the wire end with cutting pliers, then strip the insulation to expose the stranded wiring about 25/64" (10 mm) and
tightly twist the wire ends. (Fig. 4)
Using a Phillips head screwdriver, remove the terminal screw(s) on the terminal board.
Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring pressure terminal.
Place the ring pressure terminal, and replace and tighten the removed terminal screw using a screwdriver. (Fig. 5)
Stranded wire
Strip 25/64"
(10 mm)
Ring
pressure
terminal
Special
washer
Screw
Ring pressure
terminal
Wire
Terminal board
Screw and
Special washer
Wire
Ring
pressure
terminal
Fig. 4
Fig. 5
CAUTION
Loose wiring may cause the terminal to overheat or result in unit malfunction.
A fire hazard may also occur.
Therefore, ensure that all wiring is tightly connected.
8-3-5-5. Installation to the Solenoid Valve Relay Kit
Install the solenoid valve relay kit into the indoor unit and fix it using a Philips-head screwdriver.
WARNING
Do not install outside the building and the area where the water is splashed. Failure to do
so could result in product or property damage.
Do not handle or touch the unit with wet hands. Failure to do so could result in electric shock.
●
●
Regarding the solenoid valve relay kit, refer to the indoor unit Installation Instructions.
*
8. Optional Parts