Design of 3WAY VRF SYSTEM
2
- 27
1
2
3
4
5
6
7
8
9
3. ELECTRICAL WIRING
Design of 3WAY VRF SYSTEM
Wiring sample
Wiring panel
(Front)
Wiring panel
(Bottom)
Electronic component box
Earth terminal *
3
Fit wires with cable clamps.
Fit power supply and Inter-unit
control wires with cable clamps
respectively (field supply).
Terminal board for power supply
3P terminal board *
2
Inter-unit control wiring (U1, U2)
2P terminal board *
1
Inter-outdoor unit control wiring (1, 2)
2P terminal board *
1
Tightening torque
lbs.inch
N · m
*1
11 3 1.25
0.25
*2
55 2
6.2
0.2
*3
73 4
8.2
0.4
Hollow to cut out opening *
4
Hollow to cut out opening
Unit: in. (mm)
*
4
ø1-3/4" (ø44) (Power supply wiring inserting port: knockout holes)
ø1-3/8" (ø35) (Power supply wiring inserting port: knockout holes)
ø7/8" (ø23) (Inter-unit control wiring inserting port: knockout holes)
ø1-3/8" (ø35) (Power supply wiring inserting port: knockout holes)
ø7/8" (ø23) (Inter-unit control wiring inserting port: knockout holes)
ø1-3/4" (ø44) (Power supply wiring inserting port: knockout holes)
*4
・
Hollow for jigsaw holes (Maximum allowed per hole is ø1-7/8" (ø48).)
・
Be sure to use waterproof conduit for electrical wiring to the outdoor unit.
・
Protective structure is necessary to avoid raindrops through wiring ports.
・
Hollow to cut out openings for wiring ports on the panel with a jigsaw.
3. ELECTRICAL WIRING
7'B⡿ྥࡅ:$<LQGE
TD831183-00_北米向け3WAY.indb 27
15/12/17 16:05:13
Summary of Contents for U-120MF2U9
Page 8: ... MEMO ...
Page 16: ... MEMO 1 8 ...
Page 82: ... MEMO 2 66 ...
Page 84: ... MEMO 3 2 ...
Page 100: ... MEMO 4 16 ...
Page 102: ...1 2 3 4 5 6 7 8 9 MEMO 5 2 ...
Page 112: ... MEMO 6 10 ...
Page 181: ...201512 ...