Design of 3WAY VRF SYSTEM
2
- 24
1
2
3
4
5
6
7
8
9
3-4. Connecting Multiple Indoor Units to a Single Solenoid Valve Kit
It is possible to connect multiple indoor units to one solenoid valve kit.
The indoor units can be controlled individually or be operated as a group.
It is possible to adopt multiple units with a common use of the solenoid valve kit per piece of refrigerant.
Categories of connected indoor unit capacities are determined by the solenoid valve kit.
Type of solenoid valve kit
Total capacity of indoor units
CZ-P160HR2U
19,100 BTU / h (5.6 kW) < Total capacity ≤ 54,600 BTU / h (16.0 kW)
CZ-P56HR2U
Total capacity ≤ 19,100 BTU / h (5.6 kW)
* If the capacity range is exceeded, use two solenoid valves connected in parallel.
Each Method (General) and Conditions
Method 3
Method 2
Method 1
Method
Connecting one indoor unit with
one solenoid valve kit
Group control is possible by
connecting multiple indoor units
to one solenoid valve kit.
Indoor units can operate
individually by connecting
multiple indoor units to one
solenoid valve kit.
Connectable number
of remote controls
Over 2 pieces
1 piece
1 piece
Possible operating
functions
Individual control
Group control
* Thermostat On/Off function is
only individual control (when
selecting the body thermostat).
Individual control available
* Mixed group control available
Possible operating
modes
Cool, Dry, Heating, Auto, Fan
Cool, Dry, Heating, Auto, Fan
Cooling, Dry, Heating, Fan
* Auto selection is impossible.
Condition
–
Mixed cooling and heating is
impossible.
Mixed cooling and heating is
impossible.
Auto selection is impossible.
Method 1
Indoor unit
Method 1
Indoor unit
Indoor unit
Method 2
Indoor unit
Method 3
Indoor unit Indoor unit Indoor unit
Method 3
Indoor unit Indoor unit Indoor unit
Solenoid
valve kit
Remote
controller
Solenoid
valve kit
Remote
controller
Solenoid
valve kit
Solenoid
valve kit
Remote
controller
Indoor unit
Solenoid
valve kit
Remote
controller
Remote
controller
Solenoid
valve kit
Remote
controller
Remote
controller
Remote
controller
Design of 3WAY SYSTEM
3. Electrical Wiring
TD831170-02̲3WAY̲201405.indb 25
2014/05/08 21:01:38
Design of 3WAY VRF SYSTEM
3. ELECTRICAL WIRING
7'B:$<BLQGE
3. ELECTRICAL WIRING
TD831183-00_北米向け3WAY.indb 24
15/12/17 16:05:12
Summary of Contents for U-120MF2U9
Page 8: ... MEMO ...
Page 16: ... MEMO 1 8 ...
Page 82: ... MEMO 2 66 ...
Page 84: ... MEMO 3 2 ...
Page 100: ... MEMO 4 16 ...
Page 102: ...1 2 3 4 5 6 7 8 9 MEMO 5 2 ...
Page 112: ... MEMO 6 10 ...
Page 181: ...201512 ...