5
5
- 22
3-WAY SYSTEM
Trouble Diagnosis
4. 3-WAY Alarm Codes
L10 Alarm
Alarm code
L10
Alarm meaning
Outdoor unit capacity not set
Alarm conditions
The outdoor unit capacity has not been set, or the setting is not allowed by the system.
Probable cause
This alarm occurs because the capacity has not been set.
Check
Connect the outdoor unit maintenance remote controller. On the outdoor unit EEPROM detailed
setting mode screen, check the value for the outdoor unit capacity (item code 81). Check that it is
not set to “0” or to a capacity that is not allowed.
Correction
If item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it correctly.
* After changing the setting, be sure to reset both the indoor and outdoor power.
Example
—
Notes
The outdoor unit maintenance remote controller is required in order to set the capacity in the outdoor
unit EEPROM.
L11 Alarm
Alarm code
L11
Alarm meaning
Installation or connection failure in a common use solenoid valve kit, miswiring of indoor unit's remote
control group
Alarm conditions
The connection system with the multiple indoor units at only one solenoid valve kit and installation
failure of "common use solenoid valve kit"
Probable cause
Installation failure of "common use solenoid valve kit" (setting from PC at test run operation)
and address setting is not made in the same series of all indoor units.
Wiring shown below that are not allowed
(1)
(1)
"Remote control group wiring with a different solenoid valve kit connected to the indoor unit
(2)
"L11" alarm occurs in the same series of all remote controllers.
*
* "L11" alarm occurs at the only target indoor unit.
The connection system with the multiple indoor units at only one solenoid valve kit and wire
connection that is not allowed
(2)
* "L11" alarm occurs at the only target indoor unit.
Remote control group wiring with a different refrigerant circuit's indoor unit
(3)
Remote control group wiring more than one (1) indoor unit with type E1 within only one
solenoid valve kit
Remote control group wiring with a different refrigerant circuit in the indoor unit
* In this case, "L11" alarm occurs at all indoor units' remote controllers.
Check
(1)
(1)
When setting "installation of common use solenoid valve kit" is made by PC, check whether the
installation change was made in the same series of all indoor units or not.
(Check the software of address setting of PC.)
Check whether the group wiring is made with the indoor unit of a different solenoid valve kit or not.
Check whether the group wiring is made with the indoor unit of a different refrigerant circuit or not.
(2) Check the condition of remote control group wiring where "L11" alarm occurs.
Check whether type E1 indoor units are connected in the group wiring or not.
* Check the model of indoor unit with the item code 10 for the detailed setting of the remote control.
(3) Check the model of indoor unit connected to a remote control group where "L11" alarm occurs.
Correction
Perform "installation of common use solenoid valve kit" from PC in the same series of all indoor units.
(2) With a common use solenoid valve kit, change into the wiring that is allowed.
Example
—
Notes
This alarm may occasionally occur when connecting the common use solenoid valve kit.
Indoor unit
Except
Type E1
Type E1
Solenoid
valve kit
Remote
controller
Remote
controller
Indoor unit
Except
Type E1
Except
Type E1
Indoor unit
Solenoid
valve kit
Remote
controller
Remote
controller
Indoor unit
Except
Type E1
Type E1
Indoor unit
Solenoid
valve kit
Solenoid
valve kit
Remote
controller
Remote
controller
Indoor unit
Remote
controller
Indoor unit
Solenoid
valve kit
Indoor unit
Indoor unit
Indoor unit
Solenoid
valve kit
Remote
controller
Remote
controller
Remote
controller
Indoor unit
Remote
controller
Indoor unit
Solenoid
valve kit
Indoor unit
Indoor unit
Indoor unit
Solenoid
valve kit
Remote
controller
Remote
controller
Remote
controller
Indoor unit
Remote
controller
Indoor unit
Solenoid
valve kit
Indoor unit
Indoor unit
Indoor unit
Solenoid
valve kit
Remote
controller
Remote
controller
Remote
controller
Indoor unit
Remote
controller
SM830188-01̲3WAY.indb 22
SM830188-01̲3WAY.indb 22
2011/11/15 23:04:31
2011/11/15 23:04:31