- 9
3-WAY SYSTEM
Outdoor Unit Maintenance Remote Controller
3
4. Monitoring Operations
Display the indoor unit and outdoor unit sensor
temperatures.
<Operating procedure>
➀
Press and hold the
(CHECK) button and
buttons simultaneously for 4 seconds or longer to
switch to temperature monitor mode.
During temperature monitoring,
is lit.
(The display and operations are the same as
when monitor mode is started from the unit remote
controller.)
➁
Press the
button and select the indoor unit
to monitor.
➂
Use the temperature setting
and
buttons to select the item code of the temperature to
monitor.
The selected indoor unit No. and the temperature
data are displayed.
➃
To end monitoring, press the
(CHECK) button.
The display returns to the normal display.
NOTE
The display does not blink.
1
4
2
3