216
14. Outdoor Unit Protection Control
14.1 Cooling Oil Return Control
•
Oil Return control will operate 1 cycle for every 3 hours of compressor accumulation run times (normal cooling
operation mode continuously).
•
Cooling oil return control will take 5 minutes to complete.
•
During the control, Outdoor unit is fixed in cooling refrigerant cycle operation with fixed compressor frequency
and all indoor’s expansion valves are fixed open (even the indoor is in OFF operation or thermo OFF).
•
Compressor accumulation run time counter will be reset when below conditions happened :
o
Completion of cooling oil return control.
o
System operation mode changed.
14.2 Heating Oil Return Control
•
This control will operate 1 cycle if either 1 of below conditions fulfilled:
o
Every 3 hours of compressor accumulation run times (normal heating operation mode continuously).
o
Max Heat Exchanger Temperature (thermo ON) – Min Heat Exchanger Temperature (thermo OFF) > 15°C
for 3 minutes continuously.
•
During the control, Outdoor unit is continued in heating refrigerant cycle operation and expansion valve for indoor
units (thermo OFF / stand-by) will be fully opened (for one minute) one at a time sequentially started from indoor
unit with lowest Heat Exchanger Temperature (thermo OFF).
•
Compressor accumulation run time counter will be reset when below conditions happened :
o
Completion of heating oil return control.
o
All indoor units thermo ON at 3rd hour of accumulation.
o
System operation mode changed.
o
Deice
control
activated.
14.3 Overload Control
•
Overload control will operate if either 1 of below conditions happened :
o
During
Cool
Mode
Outdoor heat exchanger temp > +58°C for 10 seconds.
o
During Heat Mode
Outdoor heat exchanger temp < -30°C when outdoor ambient > -5°C
Outdoor heat exchanger temp < -35°C when outdoor ambient
≤
-5°C
•
Every interval of 30sec, compressor frequency will reduce 10% if the outdoor heat exchanger temperature still at
down zone.
•
The compressor frequency will only reduce max 3 times OR to minimum frequency.
•
For Heat operation, If compressor already reduced to minimum level but temp still at down zone, gas bypass
valve will opens.
14.4 Low Load Control
•
Low Load control will operate if either 1 of below conditions happened :
o
Indoor heat exchanger temp < 0°C during cooling operation.
o
Indoor heat exchanger temp > 54°C for 5 seconds during heating operation.
•
Every interval (15 seconds for cool mode; 30 seconds for heat mode), compressor frequency will reduce 10% if
the indoor heat exchanger temp still at down zone.
Down
zone
0
o
C
3
o
C
5
o
C
Free
zone
Unchanged
zone
Cooling Operation
Down
zone
0
o
C
3
o
C
5
o
C
Free
zone
Unchanged
zone
Cooling Operation
Free
zone
Down
zone
52
o
C
54
o
C
Heating Operation
Free
zone
Down
zone
52
o
C
54
o
C
Heating Operation
•
The compressor frequency will only reduce to minimum frequency.
•
If compressor already reduced to minimum level but temp still at down zone, gas bypass valve will opens.
Free
zone
Down
zone
54
o
C
56
o
C
58
o
C
Unchanged
zone
Cooling Operation
Free
zone
Down
zone
54
o
C
56
o
C
58
o
C
Unchanged
zone
Cooling Operation
Unchanged
zone
Free
zone
Down
zone
-30
o
C
-25
o
C
Heating (Outdoor >- 5
o
C)
Unchanged
zone
Free
zone
Down
zone
-30
o
C
-25
o
C
Heating (Outdoor >- 5
o
C)
Unchanged
zone
Free
zone
Down
zone
-35
o
C
-30
o
C
Heating (Outdoor
≤
- 5
o
C)
Unchanged
zone
Free
zone
Down
zone
-35
o
C
-30
o
C
Heating (Outdoor
≤
- 5
o
C)
Summary of Contents for S-22KA1E5
Page 4: ...4 23 6 Heating 430 24 Exploded View and Replacement Parts List451 24 1 Indoor Unit 451...
Page 12: ...12...
Page 40: ...40 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5...
Page 42: ...42 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5...
Page 44: ...44 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5...
Page 45: ...45 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5...
Page 51: ...51 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series...
Page 52: ...52 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...
Page 53: ...53 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...
Page 54: ...54 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series...
Page 55: ...55 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...
Page 56: ...56 7 6 Outdoor Unit LA1E5 Series...
Page 57: ...57 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series...
Page 58: ...58...
Page 59: ...59 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...
Page 60: ...60...
Page 61: ...61 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...
Page 62: ...62...
Page 63: ...63 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series...
Page 64: ...64...
Page 65: ...65 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...
Page 66: ...66...
Page 67: ...67 8 6 Outdoor Unit LA1E5 Series...
Page 68: ...68...
Page 70: ...70 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE...
Page 74: ...74 9 6 Outdoor Unit LA1E5 Series 9 6 1 Main PCB...
Page 76: ...76 9 6 3 Capacitor PCB DCN IN DCN OUT DCP IN DCP OUT...
Page 195: ...195...
Page 201: ...201...