AHU Kit – Installation Instructions – 07/2023
Parameter settings
9
Code No. Item
Data
Description
2E
“T10” terminal switching for terminal contacts
T10.1 & T10.2
0000
In case of pulse signal (JP001 on AHU main PCB A1 closed)
for each pulse signal change from current operation ON to OFF
respectively from current OFF to ON state
In case of static signal (JP001 on AHU main PCB A1 open) NC =
operation ON, NO = operation OFF
0001
“OFF reminder function”
With JP001 on AHU main PCB A1 closed: NC = RC operation
possible, NO = operation OFF and RC usage prohibited
JP001 on AHU main PCB A1 open: NC = no change, NO = unit
operates at upper temperature limit setting in cooling and at lower
temperature limit setting in heating (does not work in Fan mode
or Auto mode)
0002
“Fire alarm function”
JP001 status invalid. NC = operation stop and RC prohibited, NO
= RC usage possible
31
Ventilation fan operation for PACi terminal
contacts FD1 & FD2, for VRF terminal
contacts F1 & F2
0000
RC key of additional ventilation fan operation not used
0001
Additional fan operation can be used by RC key
32
Wired RC sensor
0000
Not used (TA sensor used for temperature control), factory default
0001
RC sensor used for temperature control
33
RC display °C or °F
0000
°C (factory default)
0001
°F
36
Display room temperature on RC
0000
Room temperature not displayed, only set temperature displayed
0001
Room temperature displayed
37
Defrost symbol displayed on RC
0000
Defrost not displayed
0001
Defrost displayed
3A
Discharge temperature control only for VRF
0000
Discharge temperature control through BL sensor not active
0001
Discharge temperature control through BL sensor active (only for
VRF not PACi)
3B
RAP valve control only for VRF
0000
No RAP valve control
0001
With RAP valve control
3C
Heat exchanger control temperature for cold
draft prevention in heating mode
-001 … 0026
For the first 6 minutes after heating operation start, the fan
remains OFF until max. E1, E2 or BL temperature exceeds the
set value + 10 K. If 3B = 0001, the temperature limit value is
shifted down by 17 K.
3d
Fan output switching for terminals OP6 &
OP1
0000
Output signal linked with fan. (ON when AHU unit fan is
operating.)
0001
Output signal only during dedicated FAN mode
42
Fan delay after cooling stop
0000 … 0120
Delay in seconds for Fan signal after cooling operation stop
43
Fan delay after heating stop
0000 … 0120
Delay in minutes for Fan signal after heating operation stop
5E
Humidifier ON time (ON time per 60 seconds)
0000 … 0060
Only VRF: HU1 & HU2 terminal output signal
86
Fan operation when cooling thermostat OFF
(Only PACi)
0000
No control
0001
Fan X minutes (code 87), no fan Y minutes (code 88)
0008
Fan stop
87
Fan ON time for cooling thermostat OFF
(Only PACi)
0000
0 minutes
0001
3 minutes
0002
5 minutes
88
Fan OFF time for cooling thermostat OFF
(Only PACi)
0000
0 minutes
0001
10 minutes
0002
30 minutes
0003
60 minutes