No. SX-DSV03335 - 38-
R2.0
Industrial Device Solution Business Unit, Panasonic Corporation
Size G 200 V
Use terminal blocks.
Terminal
No.
(Upper to
bottom)
Symbol
Name
Description
Up
p
er
1
L1C
Control power
input terminal
Single phase 200 - 240 V
+ 10 %
- 15 %
50/60 Hz
2
L2C
Lo
we
r
1
L1
Main power input
terminal
3 phase
200 - 240 V
+ 10 %
- 15 %
50/60 Hz
2
L2
3
L3
4
P
Regenerative
resistor connecting
terminal
To use an external regenerative resistor (customer prepared), connect an
external regenerative resistor between P and B.
In addition, parameter setting is required for the regenerative resistor.
For details, refer to "Technical Reference - Functional Specification ".
Do not connect anything to the N terminal.
5
B
6
N
7
U
Motor output
terminal
Connect each phase of the motor winding.
U: U phase V: V phase W: W phase
8
V
9
W
Earth
Earth terminal for grounding
Connector
Pin No.
Symbol
Name
Description
XE
1
DB1
External
Dynamic brake
Control connection
· This is a terminal for controlling the electromagnetic contactor (MC) for
external dynamic brake resistor (customer preparation). Please connect if
necessary.
· The applied voltage between DB1 and DB2 must be AC 300 V or less, DC
100 V or less
2
DB2
*Tighten the Earth screw with a torque of M5: 1.8 to 2.0 N · m.
*Tighten the terminal block (control power) screw with a torque of M4: 0.7 to 1.0 N · m.
If the tightening torque exceeds the maximum value, the terminal block may be damaged.
*Tighten the terminal block (main power supply, regenerative resistance, motor) screw with torque of M5: 2.0 to 2.4 N · m.
If the tightening torque exceeds the maximum value, the terminal block may be damaged
* Tighten the fixing screws for the terminal block cover with a torque of M3: 0.19 to 0.21 N · m.
If it exceeds the maximum value of tightening torque, it may be damaged.