82
Installation Manual
Parameter Item
Parameter Selection
Display
207.0V
220.0V
250.0V
265.0V
207.0V
220.0V
244.0V
255.0V
Setting
Disabled
Setting
Disabled
216.0V
〜
230.0V
235.0V
〜
255.0V
244.0V
〜
265.0V
216.0V
〜
230.0V
235.0V
〜
255.0V
244.0V
〜
265.0V
Reference
Voltage 1
Reference
Voltage 2
Reference
Voltage 3
Reference
Voltage 4
Table Volt Response Reference Values
7-11. Volt Response Reference Values Setting
Volt response mode is to respond to voltage changes at the inverter terminals, and is to increase the number of
systems which can be connected at a point on the grid without adversely affecting the voltage within an electrical
installation.
The volt-watt and volt var response modes shall use the volt response reference values.
※
Reference Voltage 4 shuld be set to be equal to or greater than Reference Voltage 3.
Australia
New Zealand
Default Set
Point
Range
Default Set
Point
Range