6.5 For Output connection
Since the transistor output is insulated from the internal circuit by a photo-coupler, it can be used both
as a NPN output and PNP (equal value) output.
・
Wire up to 100m for output connection.
6.6 RS485 Communication
・
When using shielded cable for the RS485 transmission line, ground one end.
Use a class D dedicated earth for grounding. Do not share a ground with other earth lines. (Fig.1)
・
Be sure to connect with daisy chain the RS485 transmission line between each unit.
Do not use a splitter. (Fig.2)
・
With a terminal station, RS485 (E) and RS485 (-) should be
shorted.
(Fig.1) (Fig.2)
Recommended Cable
Use the transmission cables shown below for Eco-POWER METER RS485 communication system.
Conductor Insulator
Cable
Size
Resistance
(at 20
℃)
Material Thickness
Cable
diameter
Applicable cable
1.25 mm
2
(AWG16)
or more
Max.16.8
Ω
/km
Polyethylene
Max.
0.5 mm
Approx.
8.5 mm
HITACHI
KPEV-S
1.25 mm
2
×
1P
Belden Inc. 9860
Twisted-
pair
with shield 0.5 mm
2
(AWG20)
or more
Max.33.4
Ω
/km
Polyethylene
Max.
0.5 mm
Approx.
7.8 mm
HITACHI
KPEV-S
0.5 mm
2
×
1P
Belden Inc. 9207
VCTF
0.75 mm
2
(AWG18)
or more
Max.25.1
Ω
/km
PVC
Max.
0.6 mm
Approx.
6.6 mm
VCTF
0.75 mm
2
×
2C
(JIS)
Cable Section
Twisted-pair
with shield
VCTF
Notes
1) Use shielded type twist cables.
2) Use only one type of the transmission cables.
2)
Do not mix different types of the cables.
3) Use twist pair cables under a bad noise
environment.
Pulse(
+
) Pulse(
-
)
AKW1111
⑩
⑪
AKW1110
⑪
⑫
RS485(E)
RS485(
-
)
AKW1111
⑨
⑧
AKW1110
⑩
⑨
Load
Power supply for Load
-
+
NPN output
Eco-POWER METER
Pulse (
-
)
Pulse (+)
PNP output
-
+
Eco-POWER METER
Power supply for Load
Pulse (
-
)
Pulse (+)
+
Load
-
+
-
Correct wiring
○
Incorrect wiring
×
Terminal Terminal
station station
Conductor Insulator
Jacket
Shield
Jacket
Conductor Insulator
(+)
(+)
Shielded cable
To RS-485
device
Shielded cable
Eco-POWER METER
General station
Eco-POWER METER
Terminal station
Class D grounding
Class D grounding
(-) (
E
)
(-) (
E
)
Shorted