Chapter 6 Wiring
6.1 AKW1111 (400V AC applicable type)
Be sure to wire correctly according to the terminal arrangement and wiring diagrams.
After completing wiring, be sure to attach the terminal cover for safety reasons.
6.1.1 Terminal arrangement
M3 Screw
No. Function Screw
①
L
②
N
Power supply
③
P1
④
P0
⑤
P2
⑥
P3
Measured voltage
input
M3.5 + / -
Screw
⑦
+
⑧
-
⑨
E
RS485
⑩
+
⑪
-
Pulse output
⑫
+
⑬
-
Pulse input
M3 + / -
Screw
M3.5 Screw
The input voltage to each terminal is as follows.
Terminal Phase
and
wire
Terminal Input
voltage
Operating
power supply
1P2W
①-②
100-240VAC (100 – 240V
~
)
(Line voltage)
1P2W
③-④
0-440VAC ( 0-440V
~
)
(Line voltage)
1P3W
③-④-⑤
0-220VAC ( 0-220V
~:
3W) (Phase voltage)
3P3W
③-④-⑤
0-440VAC ( 0-440V 3
~
)
(Line voltage)
Measured
voltage input
3P4W
③-④-⑤-⑥
0-254VAC ( 0-254V 3N
~
)
(Phase voltage)
6.1.2 Wiring Diagrams
・
Please connect a breaker to the voltage input part for safety reasons and to protect the device.
・
Grounding the secondary side of VT(Voltage transformer) and CT(Current transformer) is not
necessary with low-voltage circuit.
◆
When measuring a load with rated input voltage (100-200V system/ 400V system)
Single-phase two-wire system
*
One current transformer (CT) is required.
Do not wire
⑤
⑥
terminals. They are connected internal.