21
A2 hysteresis
PV/SV
, Set value
• Set the value with the
,
keys.
• Not available if
,
or
is selected during A2 type selection
Scaling low limit
PV/SV
, Set value
• Set the value with the
,
keys.
• Default value: -200
Scaling high limit
PV/SV
, Set value
• Set the value with the
,
keys.
• Default value: 1370
Decimal point place
PV/SV
, Selection
• Make a selection with the
,
keys.
• Available only for DC input
PV filter time constant
PV/SV
, Set value
• Set the value with the
,
keys.
OUT1 (Heating) low limit
PV/SV
, Set value
• Set the value with the
,
keys.
• Not available if OUT1 is ON/OFF action
OUT1 (Heating) high limit
PV/SV
, Set value
• Set the value with the
,
keys.
• Not available if OUT1 is ON/OFF action
OUT1 (Heating)
ON/OFF action hysteresis
PV/SV
, Set value
• Set the value with the
,
keys.
• Available only when OUT1 is ON/OFF action
EV1 output
PV/SV
, Selection
• Make a selection with the
,
keys.
• Not available if Heat/Cool control option is added
EV2 output
PV/SV
, Selection
• Make a selection with the
,
keys.
•
Not available if Serial communication option is added
Overlap/Dead band
PV/SV
, Set value
• Set the value with the
,
keys.
•
Available only when Heat/Cool control option is added
OUT2 (Cooling
)
ON/OFF action hysteresis
PV/SV
,Set value
• Set the value with the
,
keys.
• Available when
Heat/Cool control option is added
and when OUT2 is ON/OFF action
Input type
PV/SV
, Selection
• Make a selection with the
,
keys.
• Default value:
Output status selection
when input abnormal
PV/SV
, Selection
• Make a selection with the
,
keys.
• Available only for DC current output type with
DC input
OUT/OFF key function
PV/SV
, Selection
• Make a selection with the
,
keys.
• Selects fixed value control or program control.
Reverts to the PV/SV display.
A1 type
PV/SV
, Selection
• Make a selection with the
,
keys.
• Default value:
A1 hysteresis
PV/SV
, Set value
• Set the value with the
,
keys.
• Not available if
,
or
is selected during A1 type selection
A2 type
PV/SV
, Selection
• Make a selection with the
,
keys.
• Default value:
A1 action delayed
timer
PV/SV
, Set value
• Set the value with the
,
keys.
• Not available if
,
or
is selected during A1 type selection
Direct/Reverse control
PV/SV
, Selection
• Make a selection with the
,
keys.
• Default value:
(Reverse control action)
A2 action delayed
timer
PV/SV
, Set value
• Set the value with the
,
keys.
• Not available if
,
or
is selected during A2 type selection
AT bias
PV/SV
, Set value
• Set the value with the
,
keys.
• Not available for DC input.
(1)
(2)
(3)
Setting item not used
PV/SV
, Set value
• Do not set this item even if
is indicated
on the PV/SV display.
Input type (Character indication) and range
: K
-200 to 1370
:
-199.9 to 400.0
: J
-200 to 1000
: R
0 to 1760
: S
0 to 1760
: B
0 to 1820
: E
-200 to 800
: T
-199.9 to 400.0
: N
-200 to 1300
: PL-
0 to 1390
: C(W/Re5-26) 0 to 2315
: K
-320 to 2500
:
-199.9 to 750.0
: J
-320 to 1800
: R
0 to 3200
: S
0 to 3200
: B
0 to 3300
: E
-320 to 1500
: T
-199.9 to 750.0
: N
-320 to 2300
: PL-
0 to 2500
: C(W/Re5-26) 0 to 4200
: Pt100
-199.9 to 850.0
: JPt100 -199.9 to 500.0
: Pt100
-200 to 850
: JPt100
-200 to 500
: Pt100
-199.9 to 999.9
: JPt100 -199.9 to 900.0
: Pt100
-300 to 1500
: JPt100
-300 to 900
:
4 to 20mA DC -1999 to 9999
:
0 to 20mA DC -1999 to 9999
: 0 to 1V DC -1999 to 9999
: 0 to 5V DC -1999 to 9999
: 1 to 5V DC -1999 to 9999
: 0 to 10V DC -1999 to 9999
Alarm type
(High limit alarm): The alarm action is a
deviation setting from the SV.
The alarm is activated if the input value reaches the high limit alarm value.
(Low limit alarm): The alarm action is a
deviation setting from the SV. The
alarm is activated if the input value goes under the low limit alarm value.
(High/Low limits alarm): Combines High limit and Low limit alarm actions. When
input value reaches high limit alarm value or goes under the low limit alarm
value, the alarm is activated.
(High/Low limit range alarm): When input value is between the high limit alarm
value and low limit alarm value, the alarm is activated.
(Process high alarm)
,
(Process low alarm): Within the scale range
of the controller, alarm action points can be set at random and if the input
reaches the randomly set action point, the alarm is activated.
(High limit alarm with standby),
(Low limit alarm with standby)
(High/Low limits alarm with standby)
When the power to the controller is turned on, even if the input enters the
alarm action range, the alarm is not activated. (If the controller is allowed
to keep running, once the input exceeds the alarm action point, the standby
function will be released.)
(Timer function): If external signal enters, timer counting starts, and the action
selected during Delay action type selection is outputted after the set delay
time has elapsed.
(Pattern end output): When the program ends normally, pattern end output is
turned on. The output is maintained until it is released with the
key.
DI (Digital input) function
PV/SV
, Selection
• Make a selection with the
,
keys.
• Not available if Serial communication option is added
[Auxiliary function setting mode 2]
Press
key for 3sec while holding down the
key.
Alarm HOLD function
PV/SV
, Selection
• Make a selection with the
,
keys.
• Common setting item for A1 and A2
Not available if
,
or
is selected during A1 or A2 type selection.
Delay action type
selection
PV/SV
, Selection
• Make a selection with the
,
keys.
• Available only when
is selected during
A1 or A2 type selection.
Delay time
PV/SV
, Set value
• Set the value with the
,
keys.
• Available only when
is selected during
A1 or A2 type selection.
Step time unit
PV/SV
, Selection
• Make a selection with the
,
keys.
• Not available if
is selected during
OUT/OFF key function selection
Controller/Converter
PV/SV
, Selection
• Make a selection with the
,
keys.
• Available only for DC current output type
(4)