Operation Manual
FT128 Rev 2.4
78
The download is not completed until the following box is shown:
After the SSD download, the FT128 will restart. A number of faults may then be generated
due to the loop units being not connected yet.
Disconnected at start up
In the COM loop properties dialog box, it is possible to select the option "
Disconnected
at start up
". The COM loop will then be disabled directly after the download restarts and
therefore no faults will be generated.
Note:
A COM loop "Disconnected at start-up" can be re-connected via menu H8/S1 but
it will then be disconnected again following a new restart. Finally, the SSD for the control
unit has to be downloaded again with the option "Disconnected at start-up" not selected.
18.2.1
SSD Download to the Control Unit
Start the SSD download from EBLWin according to section 18.2.1 “SSD Download to the
Control Unit”. A text message will be shown in the FT128 display: