Operation Manual
FT128 Rev 2.4
110
24.1
Calibration of Supervised Outputs (H5/A1)
Supervised (monitored) outputs
•
The voltage outputs (S0-S1) in the control unit
•
The voltage outputs (VO0-VO1) in the COM loop output unit 3364.
•
The voltage outputs (Output 0-Output 1) on the I/O expansion board 4583
When all alarm devices (OWS, sounders, etc.) are connected, including required End-Of-
Line devices
and when the SSD download is ready, a calibration has to be done.
Function
: If the actual value differs from the calibrated value ± a small tolerance or if the
calibrated value is outside the calibration range
, a fault will be generated.
Action
Text in display
Comments
"Access"
Log on to FT128 as shown
in page 35.
Scroll to menu H5
Service
ACCEPT? H5
"A"
Calibration of supervised outputs
ACCEPT? A1
"A"
To calibrate supervised outputs press
ACCEPT
"A"
Calibration in progress
Please wait......
"A"
Calibration is completed
ACCEPT?
"A"
Calibration of supervised outputs
ACCEPT? A1
Scroll or press "Return" to
H5.
Service
ACCEPT? H5
Scroll or press "Return"
Note: During the calibration, all outputs will automatically be low, i.e. a normally high
output will be low during the calibration for a few seconds.
Note: After the calibration it is recommended to do a "Safe shutdown of control unit" (see
menu H8/S4). This will save the SSW data (e.g. the calibration values) in a Flash ROM
(see page 82).
64
Supervised (monitored) outputs can be set to be not supervised via EBLWin.
65
FT128 outputs (S0-S1) requires one EOL resistor (33K) in the last unit or one resistor (33K) in up to five units, 3364 outputs
(VO0-VO1) requires one EOL capacitor (470 nF) in the last unit or one capacitor (470 nF) in up to five units.
66
4K7 – 50K and 470 – 5x470 nF respectively.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...