117
Operation Manual
FT1020G3 Rev 2.10.4
23.3
Output Type (H2/B3)
Outputs of the same type can be collectively disabled via menu H2/B3 in a selected Control
Unit or in all Control Units.
Disabled output will stay in (or return to) the normal condition for the output respectively.
Disabled outputs are listed in menu H4/U1.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H2.
H2 Disable or re-enable
"
↲
"
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
Scroll to menu B3.
B3 Output type
Via menu B3, outputs of
the same type can be
collectively disabled in
selected control unit or
all.
"
↲
"
Disable output
type
Control outputs in Control unit 00
All
Use the soft key
"Change type of
disablements" to toggle
between:
Control
Ventilation
Extinguishing
Interlocking
Write control unit no.
when required. Press
"
↲
" to disable which will
be indicated with "
√
"
and a beep. The "type"
will be automatically
shown in the Re-enable
list
Change type of
disablements
"
↲
"
Disable output type
Control outputs in Control unit 00
All
√
-- Re-enable list (1) ---------------------------------------------
All control outputs
Use the soft key "
|
" to
toggle between
Disable
and
Re-enable
list
.
Change type of
disablements
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...