Fault messages 

The buzzer will sound continuously for any not acknowledged fault in 
the system

2

 or a fault in the unit.  The buzzer will be silenced when all 

faults  are  acknowledged  (in  any  c.i.e.)  or  with  the  push  button  "P2" 
(Silence buzzer). 

When a fault is displayed, the display back-light is turned on. 

The fault messages will be displayed on the first row in the display.   

A fire alarm has higher priority, i.e. it will be displayed instead of any 
fault message. 

Here follows a list of the fault messages that might be displayed in the 
ext. Presentation unit and in the c.i.e. respectively. 

10.1 

Fault messages in the Ext. Presentation 
Unit  (EPU) 

"General fault in system"

   Any not corrected / serviced fault 

in the system and any not acknowledged fault in the system.  To 
see the fault(s), use any c.i.e. in the system. 

"No contact with control unit"

   The contact with the c.i.e. 

is interrupted for > 45 sec.  In a brand new ext. Presentation unit 
this  message  will  be  in  English.    After  commissioning  of  the 
ext.  Presentation  unit  (i.e.  after  SSD  download)  the  message 
will be in the same language as in the c.i.e.  Check the cable, all 
connections, the 1582 / 1587 board in the EBL512 c.i.e. and the 
RS485  transceiver  component  4552  in  the  EBL128  c.i.e.    Is  a 
correct  /  complete  SSD  download  (via  Win512  /  Win128  / 
Win512 G3) performed?  Check the address setting on the 1582 
/  1587  board  in  EBL512  and  check  the  address  and  SW  mode 
settings in the ext. Presentation unit, etc. 

"SSD memory fault"

  See chapter "Restart", page 19. 

"SSD Download Memory Fault"

  in 

conjunction 

with 

SSD 

download,  see  chapter  "Commissioning  a  new  unit  /  SSD 
download", 17. 

"Memory fault in program area (n)"

  See  chapter  "Restart", 

page 19. 

10.2 

Fault messages in the c.i.e. 

10.2.1 

System EBL512 

"FAULT:  1587 board x, CU xx" 

 

Fault on / no communication to the 1587 board No. x in control 
unit  No.  xx.  Check  address  setting  and  connections  on  the 
board.  Check the programming (Win512). 

Summary of Contents for External Presentation unit 1728

Page 1: ...Technical Description MEW01297 Revision 2 External Presentation unit 1728 ver 1 4 x Author Jan Pettersson Date of issue 2010 04 08 Date of rev 2011 08 15 ...

Page 2: ...This page has deliberately been left blank ...

Page 3: ...____ 14 7 User definable text messages alarm texts ______ 16 8 Commissioning a new unit SSD download_____ 17 9 Restart ___________________________________ 19 10 Fault messages_____________________________ 21 10 1 Fault messages in the Ext Presentation Unit EPU ______ 21 10 2 Fault messages in the c i e __________________________ 21 10 2 1 System EBL512 ______________________________ 21 10 2 2 Syst...

Page 4: ...sonic Electric Works Nordic AB MEW01297 Rev 2 Technical Description External Presentation Unit 1728 ver 1 4 x 2 16 Revision history____________________________ 33 This page has deliberately been left blank ...

Page 5: ...sion 2 3 2 in EBL512 and a software version 1 0 5 in EBL128 only if the functions described below are to be used The 1728 software version 1 4 x can be used in the systems EBL512 and EBL128 with lower versions but then without the possibility to use these functions Functions2 The buzzer will sound continuously for any not acknowledged fault in the system or a fault in the unit Push button Silence ...

Page 6: ...28 ver 1 4 x 4 2 Definitions Explanations Definitions explanations abbreviations etc frequently used or not explained elsewhere in the document EPU External Presentation Unit C i e Control and indicating equipment control unit C U Control unit Control and indicating equipment S W Software H W Hardware ...

Page 7: ...xt Presentation unit shall be wall mounted 3 1 1 SW mode 1728 1587 This SW mode has the highest performance with regard to functionality response time ability to store fire alarms etc The Ext Presentation unit 1728SE running in SW mode 1728 1587 is intended to succeed the existing Display unit 2236SE and the External presentation display 2428SE In system EBL512 1728 units running in SW mode 1728 1...

Page 8: ...te the functionality performance is the same but the size the look and the front layout are different In system EBL512 1728 units running in SW mode 1728 1582 have to be connected to an Ext FBP interface board 1582 mounted in the EBL512 c i e In systems EBL128 and EBL512 G3 1728 units running in SW mode 1728 1582 can NOT be connected ...

Page 9: ...units in one specific building shall only present alarms activated within this building The following so called operands are available CU alternatives not valid for EBL128 1 Control unit CU 2 Consecutive control units CU1 CU2 3 Zone zone 4 Consecutive zones zone1 zone2 5 Zone address zone addr 6 Consecutive zone addresses zone1 addr1 zone2 addr2 Explanations 1 CU Control unit number c i e no 00 29...

Page 10: ...esentation Unit 1728 ver 1 4 x 8 Default in systems EBL512 and EBL512 G3 is Control units 00 29 i e all alarms from all c i e s will be presented in all ext Presentation units 1728 Default in system EBL128 Zones 01 32 i e all alarms will be presented in all ext Presentation units 1728 ...

Page 11: ...resentation Unit 1728 Figure 2 The Ext Presentation unit 1728SE front has the designation texts in Swedish Explanations and English texts see the following tables The following is valid in quiescent normal condition The LED L6 Operation is turned on if 24 V DC is connected and the communication with the c i e is working normally else it is turned off Buzzer is silent No text in the display and no ...

Page 12: ...shing equipment are activated 4 L4 Ventilation Brandventilation aktiverad Yellow Cont Outputs for fire smoke ventilation equipment are activated 4 L5 Fire brigade tx Larmsändare aktiverad Red Cont Output s for fire brigade tx routing equipment is are activated 4 L6 Operation Drift Green Cont 24 V DC is connected and the communication with the c i e is working normally i e the Ext Presentation unit...

Page 13: ...tinuously2 Not acknowledged fault in the system or a fault in the unit Cont All LEDs turned off as well There is a CPU memory fault in the unit Display Pre warning co incidence3 Fire alarm and Heavy smoke heat alarm presentation like in the c i e the Ext Presentation unit is connected to including a user definable text message alarm text if programmed Fault s in the system not corrected serviced a...

Page 14: ...ctions 6 1 SW mode setting A brand new ext Presentation unit has no SW mode It is factory set to Not selected and is hereby not addressable When it is powered it will automatically be ready for the SW mode setting As an alternative an ext Presentation unit in operation7 can be ready for the SW mode setting via the jumper J4 in the unit See the following chapter When the ext Presentation unit is re...

Page 15: ...turned on and the following information is shown in the display MODE SETTING Change Black Type xxxxxxxxxxxx Store Yellow Continue in accordance with chapter SW mode setting page 12 6 2 Address setting After the SW mode setting or after the language setting see above the ext Presentation unit is ready for the address setting As an alternative one10 ext Presentation unit in operation can be ready fo...

Page 16: ... the c i e One specific ext Presentation unit or all the ext Presentation units connected to the same line RS485 can in normal operation from the c i e receive a command and get ready for the Address setting directly This is done via menu H5 A9 A7 in system EBL512 G3 see Operating instructions for the system respectively 6 3 Flow chart On the following page is a flow chart showing the SW mode sett...

Page 17: ...Description External Presentation Unit 1728 ver 1 4 x 15 Power on Restart Reset via JP1 J4 ON Yes No Yes No Normal operation SW mode setting SW mode xxxx 1587 No Yes Address command from c i e Language setting Address setting SW mode selected J4 ON No No Yes Yes ...

Page 18: ...exts sent out from the c i e The priority order is as follows 1 Point alarm text stored in the ext Presentation unit 2 Zone alarm text stored in the ext Presentation unit 3 Default alarm text stored in the ext Presentation unit 4 Text sent out from the c i e When alarm texts shall be stored in all or in some ext Presentation units the unique alarm texts are created in Win512 Win128 Win512 G3 and d...

Page 19: ... on the main board 5010 in the EBL512 G3 c i e i e the ext Presentation unit s will now be powered up 3 A brand new unit will automatically be ready for the SW mode setting 4 After SW mode and address setting press P2 yellow and the unit will restart see chapter Restart page 19 5 Since the SSD is not downloaded in the c i e there will be a fault message in the ext Presentation unit s display No co...

Page 20: ...n unit s will take place During the download to an ext Presentation unit the following will be shown in its display SSD download in progress 8 After the download of SSD to an ext Presentation unit there will be shown in its display very quickly SSD Download Memory OK or SSD Download Memory Fault After that the ext Presentation unit will restart see chapter Restart page 19 9 The unit will then star...

Page 21: ...start will in the display be shown no back light Checking program memory and after that very quickly Program memory OK and after that SSD memory OK All LEDs will be turned on during the restart If there is a program memory fault there will be a fault message in the display Memory fault in program area n n 1 or 2 The ext Presentation unit will not work There will also be a fault message in the c i ...

Page 22: ...ere will be a fault message in the display SSD memory fault The ext Presentation unit will work since the alarm texts will be sent out from the c i e There will also be a fault message in the c i e In system EBL512 FAULT SSD EPU xx 1587 board x CU xx In system EBL128 FAULT Site specific data SSD EPU x In system EBL512 G3 FAULT Site specific data external presentation unit xx control unit xx ...

Page 23: ... any c i e in the system No contact with control unit The contact with the c i e is interrupted for 45 sec In a brand new ext Presentation unit this message will be in English After commissioning of the ext Presentation unit i e after SSD download the message will be in the same language as in the c i e Check the cable all connections the 1582 1587 board in the EBL512 c i e and the RS485 transceiv...

Page 24: ... interrupted Check the cable and all connections Is a correct complete SSD download via Win128 performed Check the address setting SW mode setting etc See also chapter Restart page 19 FAULT EPU x The ext Presentation unit is programmed via Win128 as another type of unit or there is a fault in the ext Presentation unit FAULT Site specific data SSD EPU x See chapter Restart page 19 10 2 3 System EBL...

Page 25: ...ic Electric Works Nordic AB MEW01297 Rev 2 Technical Description External Presentation Unit 1728 ver 1 4 x 23 FAULT Site specific data external presentation unit xx Control unit xx See chapter Restart page 19 ...

Page 26: ...d on will be displayed as General disablement in system in the 1728 unit s display When the disablement message is displayed the display back light is turned on The disablement messages will be displayed on the second row in the display A fire alarm has higher priority i e it will be displayed instead of the disablement message NOTE The disablement presentation described above is not valid in the ...

Page 27: ...tore Yellow press push button P2 yellow and the following will be displayed ADDRESS SETTING Change Black Address XX Store Yellow press push buttons P1 black and P2 yellow simultaneously and the following will be displayed Rst nn Addr aaaaaaaa Version V vvvv Return Yellow Erase SSD Black nn restart type code and aaaaaaaa memory address before restart nn 00 Power On Reset Power supply connected nn 0...

Page 28: ...xt Presentation unit icon and click the right mouse button In Win128 and Win512 G3 in menu Tools select Download FBP EPU AAU Software Select Download program and select the SW file to be downloaded i e DU_version BIN where version is the valid program version e g 14x program version 1 4 x Check set the port and baud rate See also the Win512 Win128 Win512 G3help 2 Connect the PC to the ext Presenta...

Page 29: ...s will be presented like in the c i e the ext Presentation unit is connected to including a user programmable text message alarm text if programmed See also chapter Selective alarm presentation page 7 Any not corrected serviced fault and not acknowledged fault in the system will be presented as General fault in system The buzzer sounds for any not acknowledged fault in the system 2 Any disablement...

Page 30: ...4 x 28 Figure 3 Operation summary for the Ext Presentation Unit 1728 Co incidence alarm 2 zone address dependence The buzzer sounds continuously for any not acknowledged fault in the system and Silence buzzer is possible to use 2 Any disablement in the system will be presented as General disablement in system 2 ...

Page 31: ...ions Up to 1 5 mm2 conductor area can be used Figure 4 The ext Presentation unit 1728 connections to the terminal block J1 The jumper JP8 must only be shunted if the unit is the last unit on the line NOTE In EBL128 24 V 0V S0 S1 to terminal block J1 13 14 15 16 In EBL512 G3 24 V 0V S0 S1 to terminal block J4 35 36 37 38 Figure 5 The ext Presentation unit 1728 p c b Position of the terminal block J...

Page 32: ... done J8 Not used in this unit J10 Not used in this unit J11 Not used in this unit JP1 Reset Restart of the ext Presentation unit JP2 Boot The ext Presentation unit has to be in bootstrap mode before S W download JP3 Pos A PC for S W download connected via J2 Pos B The ext Presentation unit is connected to the c i e default JP4 Pos A PC for S W download connected via J2 Pos B The ext Presentation ...

Page 33: ...tion resistor 120R has to be connected In the Ext Presentation unit this is done via jumper JP8 JP8 shunted the termination resistor is connected 15 2 1 Cable The cable to be used should be LiYCY Twisted Pairs 2 x 2 x 0 75 mm2 screened tinned copper braid or equivalent Cable length up to 1200 m theoretically Note The cable length is depending on the current consumption i e the type and number of u...

Page 34: ...ent consumption The current consumption is depending on the actual voltage on the line The following table shows the current consumption for the unit in relation to the actual line voltage min and normal respectively Unit Current consumption Quiescent mA Active mA 12 V DC 24 V DC 12 V DC 24 V DC Ext Pres unit 1728 48 26 88 42 ...

Page 35: ...n External Presentation Unit 1728 ver 1 4 x 33 16 Revision history Revisions are when possible written with red font colour Revision 1 1 Info revised 5 Info added in footnote 6 6 1 Info revised and added Revision 2 5 1 L1 L2 info added 12 1 Display text revised Info added ...

Page 36: ...Panasonic Electric Works Nordic AB MEW01297 Rev 2 Technical Description External Presentation Unit 1728 ver 1 4 x 34 ...

Page 37: ...This page has deliberately been left blank ...

Page 38: ...Panasonic Electric Works Nordic AB Jungmansgatan 12 SE 211 19 Malmö Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 info fste eu pewg panasonic com www panasonic fire security com ...

Reviews: