Technical Description External Presentation Unit 1728, ver. 1.4.x
16
7
User definable text messages
(alarm texts)
The user definable text messages (alarm texts) are depending on
which mode the unit is running in.
In SW mode 1728 - 1587
In the c.i.e., each alarm point (zone – address) and each zone can have
an individual user definable text message (alarm text)
13
presented in
the display by fire alarm, see the Planning and Operating Instructions
for the system respectively.
The alarm texts shown in the c.i.e. will also be sent to each ext.
Presentation unit and shown in its display.
As an alternative, text messages for all or selected alarm points / zones
can be stored in each ext. Presentation unit
14
. If so, these alarm texts
will be shown instead of the alarm texts sent out from the c.i.e.
The priority order is as follows:
1.
Point alarm text stored in the ext. Presentation unit.
2.
Zone alarm text stored in the ext. Presentation unit.
3.
Default alarm text stored in the ext. Presentation unit.
4.
Text sent out from the c.i.e.
When alarm texts shall be stored in all or in some ext. Presentation
units, the unique alarm texts are created in Win512 / Win128 /
Win512 G3 and downloaded when the c.i.e. site specific data (SSD) is
downloaded.
NOTE!
It is also possible to select which fire alarms that shall be
presented in the ext. Presentation unit respectively, see chapter
"Selective alarm presentation", page 7.
In SW mode 1728 - 1582
The user definable text messages (alarm texts) shown in the c.i.e. will
also be sent out to each ext. Presentation unit and shown in its display.
13
Each alarm text (up to 40 alphanumeric characters) will be shown on the
second row. The texts are created and downloaded via Win512 / Win128 /
Win512 G3.
14
At least 617 text messages can be stored in each unit.