Panasonic Eco Solutions Nordic AB
MEW01624 Rev: -
EBL128 version 2.0.x, Daily user's manual
32
10.2
Activate interlocking output (C2)
Not available for users with access level / type "Information only".
The output in each interlocking combination (Area - Point) can be
manually activated via this menu (C2). The corresponding
interlocking input will be "monitored" in the same way as if the output
was activated by its control expression. Reset of the output activated
via menu C2
has to
be performed via menu C3.
Log in with a
User name
and
Password
for typ
Building officer
(or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press
"9"
) to menu H9.
H9 Interlocking outputs and inputs
Press
"A"
to sub menu C1.
C1 Activated interlocking outputs / inputs
Scroll (or press
"2"
) to menu C2.
C2 Activate interlocking output
Press
"A"
. Use the keypad to specify Area – Point (AA and PP) for
the interlocking output to be activated.
Press
"A"
. Interlocking output AA-PP activated.
Press
"A"
. If more interlocking outputs shall be activated do as
above, if not press
"Return"
to menu C2.
Scroll to another menu or press
"Return"
to menu H9. Scroll to
another menu or leave the menu system by pressing
"Return"
.