5.6
Re-enable zone-address (B6)
Not available for users with access level / type "Information only".
Disabled alarm points (zone – address) are listed in menu H4/U1.
Re-enabling via this menu has higher priority than automatic re-
enabling.
Alarm points / zones disabled via the "Encapsulation function" have to
be re-enabled via this menu (B6) before they can activate a new alarm.
In this case a zone will be presented as ZZ - 00 (ZZ=01-99).
If there is nothing to re-enable,
--- List is empty ---
will be
shown.
Log in with a
User name
and
Password
for typ
Building officer
(or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press
"2"
) to menu H2.
H2 Disable or re-enable
Press
"A"
to sub menu B1.
B1 Disable zone
Scroll (or press
"6"
) to menu B6.
B6 Re-enable zone-address
Press
"A"
.
L
=This is a list in which you can scroll. Select an alarm
point (zone-address).
To re-enable the selected alarm point press
"A"
.
When required, re-enable more alarm points or press
"Return"
(P9)
to menu B6.
Scroll to another menu or press
"Return"
to menu H2. Scroll to
another menu or leave the menu system by pressing
"Return"
.