background image

1

MEUML-DP100 V1.1

Thank you for purchasing products from Panasonic Electric Works SUNX
Co., Ltd. Please read this Instruction Manual carefully and thoroughly for
the correct and optimum use of this product. Kindly keep this manual in a
convenient place for quick reference.

This product has been developed / produced for industrial use only.

Use within the rated pressure range.

Do not apply pressure exceeding the pressure resistance value. The
diaphragm will be damaged resulting in faulty operation.

Make sure that the power supply is off while wiring.

Incorrect wiring will damage the sensor.

Verify that the supply voltage including the ripple is within the rating.

If power is supplied from a commercial switching regulator, ensure that
the frame ground (F.G.) terminal of the power supply is connected to an
actual ground.

In case noise generating equipment (switching regulator, inverter motor,
etc.) is used in the vicinity of this sensor, connect the frame ground (F.G.)
terminal of the equipment to an actual ground.

Do not use during the initial transient time (0.5s) after the power supply is
switched on.

Do not run the wires together with high-voltage lines or power lines or put
them in the same raceway. This can cause malfunction due to induction.

The specification may not be satisfied in a strong magnetic field. 

Avoid dust, dirt, and steam.

Take care that the sensor does not come in direct contact with water, oil,
grease, or organic solvents such as thinners, etc.

Do not insert wires, etc., into the pressure port. The diaphragm will be
damaged resulting in faulty operation.

Do not operate the keys with pointed or sharp objects.

Do not apply stress directly to the sensor cable joint by forcibly bending
or pulling.

.

Use a 12mm end wrench (14mm for DP-100-E type) when tightening a
commercial coupler to the pressure port. The tightening torque should be
9.8N·m or less (M5 female connector: 1N·m or less). The commercial
coupler or pressure port section will be damaged if the tightening torque is
excessive. 
Wrap sealing tape around the coupler when connecting to prevent leaks.

INSTRUCTION MANUAL

WARNING

• Never use this product as a sensing device for personnel protection.
• In case of using sensing devices for personnel protection, use

products which meet laws and standards, such as OSHA, ANSI or
IEC etc., for personnel protection applicable in each region or
country.

• DP-100 series is designed for use with non-corrosive gas. It cannot

be used for liquid or corrosive gas.

• Japanese Measurement Laws prohibit the use of this product in

Japan.

1

CAUTIONS

2

PART NAMES

No.

Part

Description

1

Output 1 opera-
tion indicator

Lights up when comparative output 1 is 
ON

2

Output 2 / analog 
voltage operation 
indicator

Standard type

: lights up when

comparative output 2 is ON

Multifunction type

: lights up when

analog voltage output is ON

3

Pressure unit dis-
play

Depending on the model, “MPa” or “kPa” 
appears here. If you set another pressure 
unit, attach the appropriate label, e.g. psi, 
bar, etc.

4

Main display

Large 4-character LCD display.

5

Sub-display

Small 4-character LCD display.

6

Mode selection 
key

For details, see page 3, section 8, 
SELECTING MODES.

7

Up key

Increases value being set.

8

Down key

Decreases value being set.

9

4-pin male con-
nector

See “Pin assignment, 4-pin male connec-
tor” on page 2.

0

Pressure port

• DP-100 type: R1/8 + M5 female screw
• DP-100-E type: G1/8   + M5 female

screw

• DP-100-M type: M5 female screw
• DP-100-N type: NPT1/8 + M5 female

screw

3

PIPING

DP-100

1

0

9

8

7

6

5

4

3

2

12mm end wrench

Pressure Sensor

For use outside Japan

High-performance Digital Display

DP-100 

Series

Rugghölzli 2

CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for DP-100 series

Page 1: ...ightening a commercial coupler to the pressure port The tightening torque should be 9 8N m or less M5 female connector 1N m or less The commercial coupler or pressure port section will be damaged if the tightening torque is excessive Wrap sealing tape around the coupler when connecting to prevent leaks INSTRUCTION MANUAL WARNING Never use this product as a sensing device for personnel protection I...

Page 2: ...OUNTING No Part Description 1 M3 length 6mm screws with washers Accessory with MS DP1 1 2 Sensor mounting bracket MS DP1 1 Optional 5 WIRING Pin no Terminal name 1 V 2 Comparative output 1 3 Standard type Comparative output 2 Multifunction type Analog voltage output or external input 4 0V 6 I O CIRCUIT DIAGRAMS 1 2 CN 14A C غ Recommended product Contact SPHD 001T P0 5 Housing PAP 04V S JST Mfg Co ...

Page 3: ...when psi is selected as the pressure unit Hi 1 or Lo 1 is displayed for comparative output 1 and Hi 2 or Lo 2 for comparative output 2 on the sub display Notes Hysteresis can be fixed in 8 levels For details see page 6 section 11 PRO MODE Hi 1 or Lo 1 is displayed for comparative output 1 and Hi 2 or Lo 2 for comparative output 2 on the sub display 8 SELECTING MODES 9 RUN MODE Setting condition 1 ...

Page 4: ...put AREF Auto reference input 1 or ZERO Remote zero adjustment input 2 1For details see page 7 section 13 AUTO REFERENCE FUNCTION 2 For details see page 8 section 14 REMOTE ZERO ADJUSTMENT FUNCTION MULTIFUNCTION TYPE Setting condition 3 Comparative output 1 set to HYS Hysteresis mode or WCMP Window comparator mode Analog voltage output external input Analog voltage output Setting condition 4 Compa...

Page 5: ... Selects color of main display Pressure unit selection Selects desired pressure unit 1If for the standard type DP 100 comparative output 2 is set to OFF the N O N C selection normally open normally closed selection is the same as for the multifunction type i e you will only set N O or N C for comparative output 1 not for both comparative outputs 2The default setting of the high pressure type is N ...

Page 6: ... carried out for approx 5s in RUN mode the display is turned off Press any key to temporarily show the normal display Setting check code Current settings for DP 100 are stored in code which you can display See Code table on page 7 Setting copy mode Settings can be copied from master sensors to slave sensors For details see page 7 section 12 SETTING COPY FUNCTION ON settings are copied ON L setting...

Page 7: ...digit 7th digit 8th digit Analog voltage output Compara tive output 1 Compara tive output 1 Compara tive output 1 Compara tive output 1 Compara tive output 2 Compara tive output 2 Compara tive output 2 Compara tive output 2 Remote zero adjustment Auto reference N O OFF OFF N C N O N O N C N C N O N O N C N C N C N O EASY Hysteresis Window comparator EASY Hysteresis Window comparator Red when ON Gr...

Page 8: ...ot apply pressure applied at the pressure port pressure should equal atmo spheric pressure Redo zero adjustment External input is carried out outside the rated pressure range Applied pressure range should be adjusted to fall within rated pressure range Communication error e g disconnection faulty con nection etc Check the wiring when using the copy function Communication error incor rect model Mak...

Page 9: ...igits Repeatability 0 1 F S within 2 digits 0 2 F S within 2 digits 0 1 F S within 2 digits 0 2 F S within 2 digits Response time ms 2 5 5 10 25 50 100 250 500 1000 5000ms selectable Analog voltage output _ Output voltage 1 to 5V Zero point within 3V 5 F S Span within 4V 5 F S Linearity within 1 F S Output impedance approx 1k Output voltage 0 6 to 5V Zero point within 1V 5 F S Span within 4 4V 5 F...

Reviews: