Connecting to external equipment
Keep the signal input line lengths to 100 meters or less. For distances greater than
this, use a relay.
Condition
Terminal name
Alarm output
(DO 1)
Operation output
(DO 2)
Common1
(COM 1)
Circuit example
ON/OFF controller side
Name
Input/Output
item
External equipment
side
Status
output
Control
input
Non-voltage contact “a”
Static (Relay output)
Contact allowable voltage:
Max. DC30 V
Contact allowable current:
Max. 0.5 A
Minimum application load:
DC5 V 1 mA
Contact input/output terminal
Digital input
All stop:
Voltage contact “a” Pulse
(When all stop input is ON,
the stop signal is sent
periodically.)
Pulse width:
300 msec or more
All operation:
Voltage contact “a” Pulse
Pulse width:
300 msec or more
Contact allowable voltage:
DC24 V±10 %
Contact allowable current:
Max. 10 mA
All stop input
(Di 1)
Input 1
Output
DC24 V
COM
All operation input
(Di 2)
Common 2
(COM 2)
Signal terminal board
A
B
C
D
E
OUTPUT
INPUT 1
F
A. Common 2 (COM 2)
B. All stop input (Di 1)
C. All operation input (Di 2)
D. Common 1 (COM 1)
E. Alarm output (DO 1)
F. Operation output (DO 2)