Operating Instructions
Intelligent Controller
20
Preparations before changing settings
Preparation
Initial settings
The initial settings are those items that require setting after the unit is installed so that the system operates normally
.
The unit will operate normally if you make settings according t
o the following flow for the type of operation
intended.
: Settings required.
: Settings may be required.
: Settings not required.
Step
Category step
Setting
Screen menu names
Reference
page
Operation
Air
conditioning operations
only
Distribution rate
display only
Quantity used, charges display
Time
Load
Time
Load
1
Date settings
Setting the current date and time
Date settings
178
2
Composition loading
Confirming the connection configuration
Check configuration
—
3
Unit related
Central address*
1
I/D unit settings
141
Name of the indoor units
I/D unit settings
141
Distribution group
I/D unit settings
141
Area group
I/D unit settings
141
*
2
Control group
I/D unit settings
141
Not batch, not managed
I/D unit settings
141
Name of the outdoor units
O/D unit settings
145
Local remote controller prohibition setting
A/C communication settings
184
4
Group related
Name of the area group
Area group name settings
153
*
2
Name of the distribution group
Distribution group settings
155
Name of
the
schedule group
Schedule group name settings
151
5
Pulse meter related
Association with the distribution group
Pulse meter settings
158
Type of pulse meter (electricity/gas), multiplying factor (number of pulse units)
Pulse meter settings
158
Name of the pulse meter
Pulse meter settings
158
6
Distribution related
Distribution modes (time/ load)
Distribution mode settings
160
Power distribution calculation target*
3
Distribution mode settings
160
Energy saving distribution setting
Distribution mode settings
160
*
4
*
4
Distribution of gas for power generation
Distribution mode settings
160
*
5
*
5
Setting the monthly cut-of
f
days
Calendr sttngs for distr calc
148
*
6
Setting the regular hour range
Calendr sttngs for distr calc
148
Setting specified days
Calendr sttngs for distr calc
148
Currency for electricity or gas charges*
7
Distribution Ratio settings
161
Setting the capacity of the indoor units*
8
I/D unit settings
141
Setting the capacity of the electric heater*
9
I/D unit settings
141
7
Scheduling related
Schedule for a single day
Schedule setting
43
Allocating a schedule to a calendar
Calendar
49
Schedule group
I/D unit settings
141
8
Event control
Input point (names and conditions)*
10
Event control
162
Output point (names and operation)*
11
Event control
162
21
Preparations before changing settings
Preparation
Initial settings
Step
Category step
Setting
Screen menu names
Reference
page
Operation
Air
conditioning operations
only
Distribution rate
display only
Quantity used, charges display
Time
Load
Time
Load
9
Network related*
12
IP
address, net mask,
DHCP
, etc.
Network settings
123
Setting to send alarm mails
Email settings
168
User ID, password, privileges
W
eb user settings
125
10
Intelligent controller related
Buzzer volume
Display/V
olume settings
173
Brightness of the back light
Display/V
olume settings
173
Auto logout time
Display/V
olume settings
173
Identification number
Initialize
176
Initialise the days accumulated data*
13
Initialize
176
*1
Attention needs to be paid to administration divisions when devices such as systems controllers are to be used in conjunction w
ith this unit.
*2
Settings required when area administration is to be performed.
*3
Select the object of calculations for electricity distributing from the following:
Operating hours
Select when consideration is to be paid to the electricity for the indoor units.
The electricity for outdoor units and indoor units are both
loaded into this unit and distributed.
Thermostat on times
Select when no consideration is to be paid to the electricity for the indoor units.
The electricity for outdoor units only is loaded into this
unit and distributed.
*4
If the air conditioning units included in the system are multi-function types supporting simultaneous heating and cooling or i
ce thermal storage models, settings
are required.
*5
Settings are required only when units are GHP
with generators.
*6
Settings are required when only the accumulation operating time is to be managed.
*7
This must be set if you want to display charges.
*8
This only needs to be set for interface adaptors. (→“Interface
adaptors (sold separately)” (P
.198))
*9
This is used when calculating load distributing.
*10
Set items such as batch startup and stopping from external input.
*11
Set items such as batch alarm output to external devices.
*12
Required when logging in through a network device to operate and monitor
.
*13
Clears the data calculated from test operation of the air conditioning units before hand over
.