If gap is still left between the ceiling and the decoration panel
after screwing the screws, readjust the indoor unit body height.
(Refer to Fig. 6)
(3) Wiring of the decoration panel (Refer to Fig. 7)
6
Connect the connectors for swing flap motor lead
wire installed on the decoration panel.
If connectors are not connected, the malfunction
display (A7) appears on the remote controller.
Connect the connectors properly.
Make sure that the swing flap motor lead wire is not
caught between the indoor unit and the decoration
panel.
INSTALLATION OF SUCTION GRILLE AND SERVICE COVER
(1) Install the suction grille
Install by reversing the procedure shown in “PREPARATION OF DECORATION PANEL”.
It is possible to install the suction grille in 4 directions by turning the suction grille.
Change the direction when adjusting the direction of the suction grille of multiple units or in meeting customers’ demands.
NOTE)
Be careful not to get swing flap motor lead wire get caught when installing the suction grille.
(2) Install the service cover on the corner.
1
Attach the string of the service cover to the pin of the
decoration panel as in Fig. 8.
Adjustment of the indoor unit body height from the holes
in the corner of the decoration panel is possible if the
indoor unit is kept leveled and the drain piping, etc. is
unaffected.
No gap is allowed
Fig. 6
〈
Wiring Instruction Diagram
〉
(It differs from the actual state)
Fig. 7
6
Pin
Fig. 8
Install the service cover
by sliding 4 latches to fit
into the holes on the
decoration panel.
2
Install the service cover over the decoration panel.
▲
▲
▲
Indoor unit
side
Decoration
panel side
BYC125-W1(8)-(E)
01.9.13, 8:56 AM
3