Air Conditioner Service Manual

original running state automatically.

2) To press the emergency button and power on the unit, and hold on for 10 seconds, The buzzer
will ring

three times

, after this operation, the auto restart function is activated

3) To close auto restart function while it is activated, repeat process as above 2), the buzzer will ring
four times.

9. Protection/ Troubleshooting.

1) Compressor’s protection:

a

.

The PCB which has Auto-restart function, once this function is started up, the compressor goes

along 3min delay protection when power on. If the PCB hasn’t been started up Auto-restart
function, even when the PCB is power-on, the compressor doesn’t process 3 min delay function.

b

.

The compressor’s 3 min interval protection: the compressor can’t start-up until it stops 3 min later.

(except for defrosting process).
c

After the compressor started, the compressor’s state isn’t subjected to the changes on ST,RT in 3min.

2) Anti-frosting protection of indoor evaporator (cooling mode):

If IPT ≤ 0

detected in consecutive 3 min, compressor and outdoor fan motor stopped, indoor fan

motor runs at high-speed forcibly; if IPT ≥ 5

detected 3min later, then outdoor fan mot or and

compressor activated, indoor fan motor restores the original state.

3) The following table shows the fault protections. When failures happens, the PCB alarms and
buzzer rings three times. Failure code appears, and the PCB operates protection procedures.

Failure code: For the machine with LED display, the code shows on LED, for machine without LED,
the code reflects by the running light.

Failure

Running Light Flash

LED Display

RT Sensor Failure

Once / Period

E1

IPT Sensor Failure

Twice / Period

E2

Indoor Fan Motor Failure

6 times / Period

E6

When failure happened, the code is displayed statically, if there are several failure codes should be
reported at the same time, then failure codes appears one by one every eight seconds
correspondingly.
a. Sensor’s failure protection: when the sensor’s temperature is out of the range -50 ≤ T ≤ 110

,

then sensor failure is determined. Once RT, IPT sensor failures appear, the compressor stops and
indoor and outdoor fan motors shut off. Remote controller doesn’t response to any signal except for
shutdown. During failure the machine can run in fan mode. After the failure is settled, the PCB
restores to standby status.
b. Failure protection of Indoor PG fan motor: If there is no feedback signal of rotate speed within 5s,
the indoor fan motor stops, meanwhile, the compressor, outdoor fan motor, four-way valve and
auxiliary electric heater etc. cut down. 10 seconds later, the indoor fan motor restarts again, once
there is no feedback signal of rotate speed within 5 seconds either, then the machine stops and
goes into indoor fan motor failure protection, buzzer rings three times, and running light flashes at 6
times per 8 seconds. When the failure is confirmed, once there is feedback signal, the failure is
relieved automatic.

7

Summary of Contents for CU-UV5RKP

Page 1: ...NTS 1 IMPORTANT NOTICE 1 2 SPECIFICATION 2 3 OPERATION DETAILS 4 4 WIRING DIAGRAM 8 5 EXPLOSION VIEW 12 6 PARTS LIST 14 7 Disassemblymethod 18 Models CS UV5RKP CU UV5RKP CS UV9RKP CU UV9RKP Panasonic...

Page 2: ...information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior...

Page 3: ...0 Compressor Type Rotary Rotary Motor Type Single phase induction Single phase induction Output Power W 395 660 Indoor Fan Type Cross flow Cross flow Material ASG30 ASG30 Motor Type PG PG Input power...

Page 4: ...Lenghth mm 600 600 Indoor Heat Exchanger Fin Material Hydrophilic aluminium Hydrophilic aluminium Fin Type window window Row x Stage x FPI 2x 362 x16 9 2x 403 x16 9 Size W x H x L mm 25 4x231x544 25 4...

Page 5: ...ng on the air conditioner type you have purchased as follows Press any button when the arrowhead flashes on the front of Cool Cooling Only is set Press any button when the arrowhead flashes on the fro...

Page 6: ...resumed if the auto restart function activated power down after power on while if the auto restart function isn t activated the A C enters standby state Cooling only Mode Initial RT Initial ST Cooling...

Page 7: ...an 10 hours the displayed time is shown by 0 5 hour as the unit when the time fixed is more than or equal to 10 hours the displayed time is shown by 1 hour as the unit 7 Emergency switch ON OFF 1 When...

Page 8: ...lure code appears and the PCB operates protection procedures Failure code For the machine with LED display the code shows on LED for machine without LED the code reflects by the running light Failure...

Page 9: ...Air Conditioner Service Manual WIRING DIAGRAM INDOOR UNIT CS UV5RKP CS UV9RKP OUTDOOR UNIT CU UV5RKP CU UV9RKP 8...

Page 10: ...Air Conditioner Service Manual PCB layout 9...

Page 11: ...Cabinet Carton Cover Forming Base Carton Base Foaming Indoor Carton Left Foaming Right Foaming Air Conditioner Service Manual 10...

Page 12: ...Air Conditioner Service Manual EXPLOSION VIEW INDOOR UNIT CS UV5RKP CS UV9RKP 1 5 6 1 4 1 1 1 3 1 2 8 1 0 9 7 1 5 4 3 2 1 8 1 7 1 6 2 2 2 3 2 0 1 9 2 1 2 5 2 4 2 6 11...

Page 13: ...Air Conditioner Service Manual OUTDOOR UNIT CU UV5RKP CU UV9RKP 1 0 1 1 1 2 1 3 9 8 6 7 5 1 7 1 4 1 5 1 6 1 8 1 9 2 4 2 3 2 2 2 1 2 0 4 3 2 2 5 1 2 6 12...

Page 14: ...CWC70110011 Drainage Hose 1 15 CWC0705928A Display PCB Cover 1 16 CWC0900944A Display PCB Digital 1 17 CWC70040004 Cable Clamp 1 18 CWC0900994A Main PCB Digital 1 19 CWC0705987 Electrical Box 1 20 CWC...

Page 15: ...ipe 1 14 CWC0800528 Base 1 15 CWC20120025 Two way Valve 1 16 CWC81990013 Valve Supporter 1 17 CWC20130039 Three way Valve 1 18 CWC81990012 Right Plate 1 19 CWC73521301A Electrical Box Cover 1 20 CWC80...

Page 16: ...inage Hose 1 15 CWC0705928A Display PCB Cover 1 16 CWC0900944A Display PCB Digital 1 17 CWC70040004 Cable Clamp 1 INDOOR UNIT CS UV9RKP 17 CWC70040004 Cable Clamp 1 18 CWC0900994A Main PCB Digital 1 1...

Page 17: ...ipe 1 14 CWC0800528 Base 1 15 CWC20120025 Two way Valve 1 16 CWC81990013 Valve Supporter 1 17 CWC20130039 Three way Valve 1 18 CWC81990012 Right Plate 1 19 CWC73521301A Electrical Box Cover 1 20 CWC80...

Page 18: ...t open In the case of repairs to parts of the refrigerant circuit it maybe necessary that not only the workman but also a second person shall be present for observation and assistance Necessary protec...

Page 19: ...drainage assembly 6 Take out the screw cover and remove screws fixing on the frame 7 Unfasten the front panel and pull forward it slightly 2 circled positions hooked 8 Take the display PCB cover off...

Page 20: ...9 Take out the face frame 10 Remove 2 screws and take out the electronic box cover 19 Air Conditioner Service Manual...

Page 21: ...11 Remove the screws 3 connectors and take out the control box 12 Take out the water drainage assemble 20 Air Conditioner Service Manual...

Page 22: ...t Pipe Fixer 14 Take out the evaporator 15 Loosen the screw of cross flow fan and separate the cross flow fan and fan motor 16 Remark When assembling insert the cross flow fan to the ring position Rin...

Page 23: ...e 1 Remove the fixed screw and control box cover 2 Take out the 2 screws on the right side of top plate 3 Take out screws on the left side of top plate 4 The screws on the left side of grille removed...

Page 24: ...ved 6 The screws on the left and back side of grille supporter removed 7 The screws on the right side of right plate removed 8 Unscrew screws on the back side of right plate and removed the right plat...

Page 25: ...9 Remove the 3 screws fixed on the control box 10 Remove the flange nut and take out the outdoor fan 24 Air Conditioner Service Manual...

Page 26: ...Cooling characteristic 5k 25 Air Conditioner Service Manual...

Page 27: ...Cooling characteristic 9k 26 Air Conditioner Service Manual...

Page 28: ...C10902 P0C11001 P0C11002 P0C11101 P0C11102 P0C11301 P0C11302 P0C11401 P0C11402 P0C11501 P0C11502 P0C11601 P0C11602 P0C11701 P0C11702 P0C11801 P0C11802 P0C11901 P0C11902 P0C12001 P0C12002 P0C12101 P0C1...

Reviews: